6. The distance between a store and —
(a)any minor road or any railway line shall be half; and
(b)any bridleway, footpath, footway, waterway or lightly-used road shall be one-third,
the distance shown in column 2 of the Table corresponding to the quantity of explosives shown in column 1 of the Table.
HAZARD TYPE 1 EXPLOSIVE IN A BRICK-BUILT MOUNDED STORE
1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|
Quantity of explosives (kg) | Low density distance (m) | High density distance (m) | Vulnerable building distance (m) | Reference zone radius (m) | Maximum number of dwellings in reference zone |
0.1 – 25 | 101 | - | 101 | - | - |
25 – 50 | 107 | - | 107 | - | - |
50 – 75 | 112 | - | 112 | - | - |
75 – 100 | 118 | - | 118 | - | - |
100 – 150 | 128 | 142 | 128 | 257 | 81 |
150 – 200 | 139 | 156 | 139 | 278 | 96 |
200 – 300 | 161 | 180 | 161 | 322 | 128 |
300 – 400 | 183 | - | 183 | - | - |
400 – 450 | 193 | - | 193 | - | - |
450 – 500 | 204 | - | 204 | - | - |
500 – 600 | 204 | - | 216 | - | - |
600 – 700 | 204 | 231 | 238 | 408 | 206 |
700 – 800 | 204 | 238 | 260 | 408 | 206 |
800 – 900 | 204 | 245 | 280 | 408 | 206 |
900 – 1000 | 204 | 250 | 300 | 408 | 206 |
1000 – 1100 | 204 | 255 | 319 | 408 | 206 |
1100 – 1200 | 204 | 259 | 337 | 408 | 206 |
1200 – 1300 | 204 | 263 | 354 | 408 | 206 |
1300 – 1400 | 204 | 266 | 370 | 408 | 206 |
1400 – 1500 | 204 | 269 | 386 | 408 | 206 |
1500 – 1600 | 204 | 272 | 402 | 408 | 206 |
1600 – 1700 | 208 | 274 | 416 | 416 | 214 |
1700 – 1800 | 215 | 277 | 431 | 431 | 229 |
1800 – 1900 | 222 | 279 | 444 | 444 | 244 |
1900 - 2000 | 229 | 281 | 458 | 458 | 259 |
HAZARD TYPE 1 EXPLOSIVE IN A BRICK-BUILT UNMOUNDED STORE
1 | 2 | 3 |
---|---|---|
Quantity of explosives (kg) | Low density distance (m) | Vulnerable building distance (m) |
0.1 – 25 | 141 | 141 |
25 – 50 | 160 | 160 |
50 – 75 | 180 | 180 |
75 – 100 | 199 | 199 |
100 – 150 | 230 | 230 |
150 – 200 | 256 | 256 |
200 – 300 | 293 | 293 |
300 – 400 | 320 | 320 |
400 – 450 | 331 | 331 |
450 – 500 | 340 | 340 |
500 – 600 | 355 | 355 |
600 – 700 | 367 | 367 |
700 – 800 | 377 | 377 |
800 – 900 | 385 | 385 |
900 – 1000 | 392 | 392 |
1000 – 1100 | 398 | 398 |
1100 – 1200 | 403 | 403 |
1200 – 1300 | 408 | 408 |
1300 – 1400 | 412 | 412 |
1400 – 1500 | 415 | 415 |
1500 – 1600 | 418 | 418 |
1600 – 1700 | 421 | 421 |
1700 – 1800 | 424 | 431 |
1800 – 1900 | 426 | 444 |
1900 – 2000 | 428 | 458 |
HAZARD TYPE 1 EXPLOSIVE IN A METAL-BUILT MOUNDED STORE
1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|
Quantity of explosives (kg) | Low density distance (m) | High density distance (m) | Vulnerable building distance (m) | Reference zone radius (m) | Maximum number of dwellings in reference zone |
0.1 – 25 | 34 | 45 | 40 | 68 | 6 |
25 – 50 | 37 | 45 | 48 | 74 | 7 |
50 – 75 | 40 | 45 | 54 | 80 | 8 |
75 – 100 | 43 | 48 | 66 | 86 | 9 |
100 – 150 | 49 | 55 | 86 | 97 | 12 |
150 – 200 | 54 | 62 | 104 | 109 | 15 |
200 – 300 | 68 | 76 | 136 | 136 | 23 |
300 – 400 | 83 | - | 165 | - | - |
400 – 450 | 89 | - | 178 | - | - |
450 – 500 | 96 | - | 191 | - | - |
500 – 600 | 108 | - | 216 | - | - |
600 – 700 | 119 | - | 238 | - | - |
700 – 800 | 130 | - | 260 | - | - |
800 – 900 | 140 | - | 280 | - | - |
900 – 1000 | 150 | - | 300 | - | - |
1000 – 1100 | 159 | - | 319 | - | - |
1100 – 1200 | 168 | - | 337 | - | - |
1200 – 1300 | 177 | - | 354 | - | - |
1300 – 1400 | 185 | - | 370 | - | - |
1400 – 1500 | 193 | - | 386 | - | - |
1500 – 1600 | 201 | - | 402 | - | - |
1600 – 1700 | 208 | - | 416 | - | - |
1700 – 1800 | 215 | - | 431 | - | - |
1800 – 1900 | 222 | - | 444 | - | - |
1900 - 2000 | 229 | - | 458 | - | - |
HAZARD TYPE 1 EXPLOSIVE IN A METAL-BUILT UNMOUNDED STORE WITH NO DETONATOR ANNEX ATTACHED
1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|
Quantity of explosives (kg) | Low density distance (m) | High density distance (m) | Vulnerable building distance (m) | Reference zone radius | Maximum number of dwellings in reference zone |
0.1 – 10 | 23 | 30 | 40 | 46 | 3 |
10 – 20 | 29 | 35 | 42 | 57 | 4 |
20 – 30 | 33 | 39 | 44 | 65 | 5 |
30 – 40 | 36 | 42 | 46 | 71 | 6 |
40 – 50 | 38 | 44 | 48 | 76 | 7 |
50 – 60 | 40 | 46 | 48 | 80 | 8 |
60 – 70 | 42 | 48 | 52 | 84 | 9 |
70 – 80 | 43 | 50 | 57 | 87 | 9 |
80 – 90 | 44 | 52 | 61 | 89 | 10 |
90 – 100 | 45 | 55 | 66 | 91 | 10 |
100 – 110 | 46 | 57 | 70 | 93 | 11 |
110 – 120 | 47 | 59 | 74 | 95 | 11 |
120 – 130 | 48 | 62 | 78 | 97 | 12 |
130 – 140 | 49 | 64 | 82 | 98 | 12 |
140 – 150 | 50 | 66 | 86 | 100 | 12 |
150 – 160 | 51 | 68 | 90 | 102 | 13 |
160 – 170 | 52 | 71 | 93 | 104 | 13 |
170 –180 | 53 | 73 | 97 | 106 | 14 |
180 – 190 | 54 | 75 | 101 | 108 | 14 |
190 – 200 | 55 | 78 | 104 | 110 | 15 |
200 – 300 | 68 | 101 | 136 | 136 | 23 |
300 – 400 | 83 | 124 | 165 | 165 | 34 |
400 – 450 | 89 | 135 | 178 | 178 | 39 |
450 – 500 | 96 | 138 | 191 | 191 | 45 |
500 – 600 | 108 | 144 | 216 | 216 | 57 |
600 – 700 | 119 | 150 | 238 | 238 | 70 |
700 – 800 | 130 | 156 | 260 | 260 | 83 |
800 – 900 | 140 | 162 | 280 | 280 | 97 |
900 – 1000 | 150 | 168 | 300 | 300 | 111 |
1000 – 1100 | 159 | 168 | 319 | 318 | 111 |
1100 – 1200 | 168 | - | 337 | - | - |
1200 – 1300 | 177 | - | 354 | - | - |
1300 – 1400 | 185 | - | 370 | - | - |
1400 – 1500 | 193 | - | 386 | - | - |
1500 – 1600 | 201 | - | 402 | - | - |
1600 – 1700 | 208 | - | 416 | - | - |
1700 – 1800 | 215 | - | 431 | - | - |
1800 – 1900 | 222 | - | 444 | - | - |
1900 – 2000 | 229 | - | 458 | - | - |
HAZARD TYPE 1 EXPLOSIVE IN A METAL-BUILT UNMOUNDED STORE WITH A DETONATOR ANNEX ATTACHED
1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|
Quantity of explosives (kg) | Low density distance (m) | High density distance (m) | Vulnerable building distance (m) | Reference zone radius (m) | Maximum number of dwellings in reference zone |
0.1 – 25 | 38 | 53 | 54 | 74 | 11 |
25 – 50 | 43 | 53 | 54 | 86 | 11 |
50 – 75 | 48 | 60 | 54 | 96 | 11 |
75 – 100 | 53 | 77 | 66 | 106 | 14 |
100 – 150 | 63 | 110 | 86 | 127 | 20 |
150 – 200 | 74 | 143 | 104 | 147 | 27 |
200 – 300 | 94 | 209 | 136 | 188 | 44 |
300 – 400 | 115 | 275 | 165 | 229 | 65 |
400 – 450 | 125 | 308 | 178 | 250 | 77 |
450 – 500 | 128 | 309 | 191 | 257 | 81 |
500 – 600 | 135 | 311 | 216 | 270 | 90 |
600 – 700 | 142 | 312 | 238 | 283 | 99 |
700 – 800 | 148 | 314 | 260 | 297 | 109 |
800 – 900 | 155 | 316 | 280 | 310 | 119 |
900 – 1000 | 162 | 318 | 300 | 324 | 129 |
1000 – 1100 | 169 | 319 | 319 | 337 | 140 |
1100 – 1200 | 175 | 321 | 337 | 350 | 152 |
1200 – 1300 | 182 | 323 | 354 | 364 | 163 |
1300 – 1400 | 189 | 325 | 370 | 377 | 176 |
1400 - 1500 | 195 | 326 | 386 | 391 | 188 |
1500 – 1600 | 202 | 328 | 402 | 404 | 202 |
1600 – 1700 | 209 | 330 | 416 | 417 | 215 |
1700 – 1800 | 215 | 332 | 431 | 431 | 229 |
1800 – 1900 | 222 | 333 | 444 | 444 | 244 |
1900 – 2000 | 229 | 335 | 458 | 458 | 259 |
HAZARD TYPE 2 EXPLOSIVE, SOME OR ALL ITEMS BEING OF MORE THAN 0.7 KG NET MASS
1 | 2 | 3 |
---|---|---|
Quantity of explosives (kg) | Low density distance (m) | Vulnerable building distance (m) |
0.1 – 25 | 45 | 90 |
25 – 50 | 88 | 176 |
50 – 75 | 108 | 216 |
75 – 100 | 129 | 238 |
100 – 150 | 148 | 296 |
150 – 200 | 168 | 336 |
200 – 300 | 191 | 382 |
300 – 400 | 207 | 414 |
400 – 450 | 213 | 426 |
450 – 500 | 219 | 438 |
500 – 600 | 226 | 452 |
600 – 700 | 233 | 466 |
700 – 800 | 240 | 480 |
800 – 900 | 248 | 496 |
900 – 1000 | 256 | 512 |
1000 – 1100 | 259 | 518 |
1100 – 1200 | 262 | 524 |
1200 – 1300 | 266 | 532 |
1300 – 1400 | 270 | 540 |
1400 – 1500 | 274 | 548 |
1500 – 1600 | 278 | 556 |
1600 – 1700 | 282 | 564 |
1700 – 1800 | 286 | 572 |
1800 – 1900 | 288 | 576 |
1900 – 2000 | 292 | 592 |
HAZARD TYPE 2 EXPLOSIVE, EVERY ITEM BEING OF 0.7 KG NET MASS OR LESS
1 | 2 | 3 |
---|---|---|
Quantity of explosives (kg) | Low density distance (m) | Vulnerable building distance (m) |
0.1 – 25 | 37 | 76 |
25 – 50 | 43 | 86 |
50 – 75 | 47 | 94 |
75 – 100 | 51 | 102 |
100 – 150 | 56 | 112 |
150 – 200 | 60 | 120 |
200 – 300 | 66 | 132 |
300 – 400 | 71 | 142 |
400 – 450 | 73 | 146 |
450 – 500 | 74 | 148 |
500 – 600 | 76 | 152 |
600 – 700 | 78 | 158 |
700 – 800 | 81 | 162 |
800 – 900 | 84 | 164 |
900 – 1000 | 87 | 174 |
1000 – 1100 | 88 | 176 |
1100 – 1200 | 89 | 178 |
1200 – 1300 | 90 | 180 |
1300 – 1400 | 91 | 182 |
1400 – 1500 | 92 | 184 |
1500 – 1600 | 94 | 188 |
1600 – 1700 | 95 | 190 |
1700 – 1800 | 97 | 194 |
1800 – 1900 | 99 | 198 |
1900 – 2000 | 101 | 202 |
HAZARD TYPE 3 EXPLOSIVE
1 | 2 |
---|---|
Quantity of explosives (kg) | Low density distance (m) |
0.1 – 25 | - |
25 – 50 | 23 |
50 – 75 | 25 |
75 – 100 | 29 |
100 – 150 | 33 |
150 – 200 | 37 |
200 – 300 | 42 |
300 – 400 | 47 |
400 – 450 | 47 |
450 – 500 | 50 |
500 – 600 | 51 |
600 – 700 | 53 |
700 – 800 | 54 |
800 – 900 | 55 |
900 – 1000 | 63 |
1000 – 1100 | 70 |
1100 – 1200 | 71 |
1200 – 1300 | 72 |
1300 – 1400 | 73 |
1400 – 1500 | 74 |
1500 – 1600 | 75 |
1600 – 1700 | 76 |
1700 – 1800 | 78 |
1800 – 1900 | 79 |
1900 – 2000 | 80 |
HAZARD TYPE 4 EXPLOSIVE
1 | 2 |
---|---|
Quantity of explosives (kg) | Low density distance (m) |
0.1 – 250 | 0 |
250 – 300 | 1 |
300 – 340 | 2 |
340 – 370 | 3 |
370 – 400 | 4 |
400 – 450 | 5 |
450 – 500 | 6 |
500 – 550 | 7 |
550 – 600 | 8 |
600 – 650 | 9 |
650 – 700 | 10 |
700 – 750 | 11 |
750 – 800 | 12 |
800 – 900 | 13 |
900 – 950 | 14 |
950 – 1000 | 15 |
1000 – 1100 | 16 |
1100 – 1150 | 17 |
1150 – 1200 | 18 |
1200 – 1300 | 19 |
1300 – 1350 | 20 |
1350 – 1400 | 21 |
1400 – 1450 | 22 |
1450 – 1550 | 23 |
1550 – 1600 | 24 |
1600 – 1650 | 25 |
1650 – 1700 | 26 |
1700 – 1800 | 27 |
1800 – 1850 | 28 |
1850 – 1900 | 29 |
1900 – 2000 | 30 |
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made): The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.
Explanatory Memorandum sets out a brief statement of the purpose of a Statutory Instrument and provides information about its policy objective and policy implications. They aim to make the Statutory Instrument accessible to readers who are not legally qualified and accompany any Statutory Instrument or Draft Statutory Instrument laid before Parliament from June 2004 onwards.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: