Commission Regulation (EU) No 813/2013 of 2 August 2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for space heaters and combination heaters (Text with EEA relevance)
When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.
Legislation.gov.uk publishes the UK version. EUR-Lex publishes the EU version. The EU Exit Web Archive holds a snapshot of EUR-Lex’s version from IP completion day (31 December 2020 11.00 p.m.).
This is the original version as it was originally adopted in the EU.
This legislation may since have been updated - see the latest available (revised) version
THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Having regard to Directive 2009/125/EC of the European Parliament and of the Council of 21 October 2009 establishing a framework for the setting of ecodesign requirements for energy-related products(1) and in particular Article 15(1) thereof,
After consulting the Ecodesign Consultation Forum,
Whereas:
(1) Under Directive 2009/125/EC ecodesign requirements should be set by the Commission for energy-related products representing significant volumes of sales and trade, having a significant environmental impact and presenting significant potential for improvement through design in terms of their environmental impact without entailing excessive costs.
(2) Provisions on the efficiency of boilers were established by Council Directive 92/42/EEC of 21 May 1992 on efficiency requirements for new hot-water boilers fired with liquid or gaseous fuels(2).
(3) Article 16(2)(a) of Directive 2009/125/EC provides, that in accordance with the procedure referred to in Article 19(3) and the criteria set out in Article 15(2), and after consulting the Ecodesign Consultation Forum, the Commission should, as appropriate, introduce implementing measures for products offering a high potential for cost-effective reduction of greenhouse gas emissions, such as for heating and water heating equipment.
(4) The Commission has carried out a preparatory study on the technical, environmental and economic aspects of space heaters and combination (space and water) heaters typically used in the Union. The study was devised together with stakeholders and interested parties from the Union and third countries, and the results have been made publicly available.
(5) The environmental aspects of space heaters and combination heaters that have been identified as significant for the purposes of this Regulation are energy consumption in the use phase and (for heat pump heaters) sound power levels. In addition, for heaters using fossil fuels, emissions of nitrogen oxides, carbon monoxide, particulate matter and hydrocarbons are identified as significant environmental aspects.
(6) It is not appropriate to set ecodesign requirements for emissions of carbon monoxide, particulate matter and hydrocarbons as no suitable European measurement methods are as yet available. With a view to developing such measurement methods, the Commission mandated the European standardisation organisations to consider ecodesign requirements for those emissions during the review of this Regulation. National provisions for ecodesign requirements on emissions of carbon monoxides, particulate matter and hydrocarbons of space heaters and combination heaters may be maintained or introduced until the corresponding Union ecodesign requirements enter into force. The provisions of Directive 2009/142/EC of the European Parliament and of the Council of 30 November 2009 relating to appliances burning gaseous fuels(3), which limit the combustion products of appliances burning gaseous fuels in relation to health and safety, are not affected.
(7) The preparatory study shows that requirements regarding the other ecodesign parameters referred to in Annex I, Part 1 to Directive 2009/125/EC are not necessary in the case of space heaters and combination heaters. In particular, greenhouse gas emissions related to refrigerants used in heat pump heaters for heating today’s European building stock are not identified as significant. The appropriateness of setting ecodesign requirements for these greenhouse gas emissions will be reassessed when reviewing this Regulation.
(8) The scope of this Regulation should include boiler space heaters, cogeneration space heaters and heat pump space heaters providing heat to water-based central heating systems for space heating purposes, and boiler combination heaters and heat pump combination heaters providing heat to water-based central heating systems for space heating purposes and heat to deliver hot drinking and sanitary water. These heaters are designed to use gaseous or liquid fuels, including from biomass (unless predominantly), electricity and ambient or waste heat.
(9) Heaters that are designed for using gaseous or liquid fuels predominantly (more than 50 %) produced from biomass have specific technical characteristics which require further technical, economic and environmental analyses. Depending on the outcome of the analyses, ecodesign requirements for those heaters should be set at a later stage, if appropriate.
(10) Annual energy consumption related to space heaters and combination heaters was estimated to have been 12 089 PJ (about 289 Mtoe) in the Union in 2005, corresponding to 698 Mt CO2 emissions. Unless specific measures are taken, annual energy consumption is expected to be 10 688 PJ in 2020. Annual emissions of nitrogen oxides related to space heaters and combination heaters were estimated to have been 821 kt SOx equivalent in the Union in 2005. Unless specific measures are taken, annual emissions are expected to be 783 kt SOx equivalent in 2020. The preparatory study shows that the use-phase energy consumption and emissions of nitrogen oxides of space heaters and combination heaters can be significantly reduced.
(11) The energy consumption of space heaters and combination heaters can be reduced by applying existing cost-effective non-proprietary technologies which lead to a reduction in the combined costs of purchasing and operating these products.
(12) In the Union there are almost five million dwellings with shared open-flue systems. For technical reasons it is not possible to replace existing boiler space heaters and boiler combination heaters by efficient condensing boilers in dwellings with a shared open-flue system. The requirements contained in this Regulation allow non-condensing boilers specifically designed for such a configuration to remain on the market; this is to prevent undue costs for consumers, to give manufacturers time to develop boilers dedicated to more efficient heating technologies, and to give Member States time to reflect on national building codes.
(13) The combined effect of the ecodesign requirements set out in this Regulation and the Commission Delegated Regulation (EU) No 811/2013 of 18 February 2013 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to energy labelling of space heaters, combination heaters, packages of space heater, temperature control and solar device and packages of combination heater, temperature control and solar device(4) is expected to result by 2020 in estimated annual energy savings of about 1 900 PJ (about 45 Mtoe), corresponding to around 110 Mt CO2 emissions, and a reduction in annual nitrogen oxides emissions of some 270 kt SOx equivalent, compared to what would happen if no measures were taken.
(14) Ecodesign requirements should harmonise energy consumption, sound power level and nitrogen oxides emission requirements for space heaters and combination heaters throughout the Union, thus helping to make the internal market operate better and to improve the environmental performance of these products.
(15) The ecodesign requirements should not affect the functionality or affordability of space heaters or combination heaters from the end-user’s perspective and should not negatively affect health, safety or the environment.
(16) The ecodesign requirements should be introduced gradually to give manufacturers a sufficient timeframe to redesign their products subject to this Regulation. The timing should be such that cost impact for manufacturers, in particular for small and medium-sized enterprises, is taken into account, while ensuring timely achievement of the objectives of this Regulation.
(17) Product parameters should be measured and calculated using reliable, accurate and reproducible methods which take into account recognised state-of-the-art measurement and calculation methods, including, where available, harmonised standards adopted by the European standardisation organisations under a request from the Commission, in accordance with the procedures laid down in the Regulation (EU) No 1025/2012 of the European Parliament and of the Council of 25 October 2012 on European standardisation(5).
(18) In accordance with Article 8(2) of Directive 2009/125/EC, this Regulation specifies which conformity assessment procedures apply.
(19) To facilitate compliance checks, manufacturers should provide information in the technical documentation referred to in Annexes IV and V to Directive 2009/125/EC insofar as that information relates to the requirements laid down in this Regulation.
(20) To further limit the environmental impact of space heaters and combination heaters, manufacturers should provide information on disassembly, recycling and/or disposal.
(21) In addition to the legally binding requirements laid down in this Regulation, indicative benchmarks for best available technologies should be identified to ensure that information on the life-cycle environmental performance of space heaters and combination heaters is widely available and easily accessible.
(22) Directive 92/42/EEC should be repealed, except for Articles 7(2) and 8 thereof and Annexes III to V thereto, and new provisions should be laid down by this Regulation to ensure that the scope is extended to heaters other than boilers, to further improve the energy efficiency of space heaters and combination heaters, and to improve other significant environmental aspects of space heaters and combination heaters.
(23) The measures provided for in this Regulation are in accordance with the opinion of the Committee established by Article 19(1) of Directive 2009/125/EC,
HAS ADOPTED THIS REGULATION:
1.This Regulation establishes ecodesign requirements for the placing on the market and/or putting into service of space heaters and combination heaters with a rated heat output ≤ 400 kW, including those integrated in packages of space heater, temperature control and solar device or packages of combination heater, temperature control and solar device as defined in Article 2 of Commission Delegated Regulation (EU) No 811/2013.
2.This Regulation shall not apply to:
(a)heaters specifically designed for using gaseous or liquid fuels predominantly produced from biomass;
(b)heaters using solid fuels;
(c)heaters within the scope of Directive 2010/75/EU of the European Parliament and of the Council(6);
(d)heaters generating heat only for the purpose of providing hot drinking or sanitary water;
(e)heaters for heating and distributing gaseous heat transfer media such as vapour or air;
(f)cogeneration space heaters with a maximum electrical capacity of 50 kW or above;
(g)heat generators designed for heaters and heater housings to be equipped with such heat generators placed on the market before 1 January 2018 to replace identical heat generators and identical heater housings. The replacement product or its packaging shall clearly indicate the heater for which it is intended.
In addition to the definitions set out in Article 2 of Directive 2009/125/EC, the following definitions shall apply for the purposes of this Regulation:
‘heater’ means a space heater or combination heater;
‘space heater’ means a device that
provides heat to a water-based central heating system in order to reach and maintain at a desired level the indoor temperature of an enclosed space such as a building, a dwelling or a room; and
is equipped with one or more heat generators;
‘combination heater’ means a space heater that is designed to also provide heat to deliver hot drinking or sanitary water at given temperature levels, quantities and flow rates during given intervals, and is connected to an external supply of drinking or sanitary water;
‘water-based central heating system’ means a system using water as a heat transfer medium to distribute centrally generated heat to heat emitters for the space heating of buildings, or parts thereof;
‘heat generator’ means the part of a heater that generates the heat using one or more of the following processes:
combustion of fossil fuels and/or biomass fuels;
use of the Joule effect in electric resistance heating elements;
capture of ambient heat from an air source, water source or ground source, and/or waste heat;
whereby a heat generator designed for a heater and a heater housing to be equipped with such a heat generator shall be also considered a heater;
‘heater housing’ means the part of a heater designed to have a heat generator fitted;
‘rated heat output’ (Prated) means the declared heat output of a heater when providing space heating and, if applicable, water heating at standard rating conditions, expressed in kW; for heat pump space heaters and heat pump combination heaters the standard rating conditions for establishing the rated heat output are the reference design conditions, as set out in Annex III, Table 4;
‘standard rating conditions’ means the operating conditions of heaters under average climate conditions for establishing the rated heat output, seasonal space heating energy efficiency, water heating energy efficiency, sound power level and nitrogen oxide emissions;
‘biomass’ means the biodegradable fraction of products, waste and residues from biological origin from agriculture (including vegetal and animal substances), forestry and related industries including fisheries and aquaculture, as well as the biodegradable fraction of industrial and municipal waste;
‘biomass fuel’ means a gaseous or liquid fuel produced from biomass;
‘fossil fuel’ means a gaseous or liquid fuel of fossil origin;
‘boiler space heater’ means a space heater that generates heat using the combustion of fossil fuels and/or biomass fuels, and/or using the Joule effect in electric resistance heating elements;
‘boiler combination heater’ means a boiler space heater that is designed to also provide heat to deliver hot drinking or sanitary water at given temperature levels, quantities and flow rates during given intervals, and is connected to an external supply of drinking or sanitary water;
‘electric boiler space heater’ means a boiler space heater that generates heat using the Joule effect in electric resistance heating elements only;
‘electric boiler combination heater’ means a boiler combination heater that generates heat using the Joule effect in electric resistance heating elements only;
‘cogeneration space heater’ means a space heater simultaneously generating heat and electricity in a single process;
‘heat pump space heater’ means a space heater using ambient heat from an air source, water source or ground source, and/or waste heat for heat generation; a heat pump space heater may be equipped with one or more supplementary heaters using the Joule effect in electric resistance heating elements or the combustion of fossil and/or biomass fuels;
‘heat pump combination heater’ means a heat pump space heater that is designed to also provide heat to deliver hot drinking or sanitary water at given temperature levels, quantities and flow rates during given intervals, and is connected to an external supply of drinking or sanitary water;
‘supplementary heater’ means a non-preferential heater that generates heat in cases where the heat demand is greater than the rated heat output of the preferential heater;
‘seasonal space heating energy efficiency’ (ηs ) means the ratio between the space heating demand for a designated heating season, supplied by a heater and the annual energy consumption required to meet this demand, expressed in %;
‘water heating energy efficiency’ (ηwh ) means the ratio between the useful energy in the drinking or sanitary water provided by a combination heater and the energy required for its generation, expressed in %;
‘sound power level’ (LWA ) means the A-weighted sound power level, indoors and/or outdoors, expressed in dB;
‘conversion coefficient’ (CC) means a coefficient reflecting the estimated 40 % average EU generation efficiency referred to in Directive 2012/27/EU of the European Parliament and of the Council(7); the value of the conversion coefficient is CC = 2,5.
For the purposes of Annexes II to V, additional definitions are set out in Annex I.
1.The ecodesign requirements for heaters are set out in Annex II.
2.Each ecodesign requirements shall apply in accordance with the following timetable:
(a)from 26 September 2015:
heaters shall meet the requirements set out in Annex II, points 1(a), 3 and 5;
combination heaters shall meet the requirements set out in Annex II, point 2(a);
(b)from 26 September 2017:
electric space heaters, electric combination heaters, cogeneration space heaters, heat pump space heaters and heat pump combination heaters shall meet the requirements set out in Annex II, point 1(b);
combination heaters shall meet the requirements set out in Annex II, point 2(b);
(c)from 26 September 2018 heaters shall meet the requirements set out in Annex II, point 4(a).
3.Compliance with ecodesign requirements shall be measured and calculated in accordance with the requirements set out in Annex III.
1.The conformity assessment procedure referred to in Article 8(2) of Directive 2009/125/EC shall be the internal design control set out in Annex IV to that Directive or the management system set out in Annex V to that Directive without prejudice to Articles 7(2) and 8 of and Annexes III to V to Council Directive 92/42/EEC.
2.For the purposes of conformity assessment, the technical documentation shall contain the product information set out in point 5(b) of Annex II to this Regulation.
When performing the market surveillance checks referred to in Article 3(2) of Directive 2009/125/EC to ensure compliance with the requirements set out in Annex II to this Regulation, the Member States’ authorities shall apply the verification procedure set out in Annex IV to this Regulation.
The indicative benchmarks for best-performing heaters available on the market at the time of entry into force of this Regulation are set out in Annex V.
The Commission shall review this Regulation in the light of technological progress with heaters and present the result of that review to the Ecodesign Consultation Forum no later than five years from the date of entry into force of this Regulation. In particular, the review shall include an assessment of the following aspects:
the appropriateness of setting ecodesign requirements for greenhouse gas emissions related to refrigerants;
on the basis of the measurement methods under development, the level of the ecodesign requirements for emissions of carbon monoxide, hydrocarbons and particulate matter that may be introduced;
the appropriateness of setting stricter ecodesign requirements for the energy efficiency of boiler space heaters and boiler combination heaters, for the sound power level and for emissions of nitrogen oxides;
the appropriateness of setting ecodesign requirements for heaters specifically designed for using gaseous or liquid fuels predominantly produced from biomass;
the validity of the conversion coefficient value;
the appropriateness of third party certification.
1.Until 26 September 2015 Member States may allow the placing on the market and/or putting into service of heaters which are in conformity with the national provisions in force when this Regulation is adopted regarding seasonal space heating energy efficiency, water heating energy efficiency and sound power level.
2.Until 26 September 2018 Member States may allow the placing on the market and/or putting into service of heaters, which are in conformity with the national provisions in force when this Regulation is adopted regarding emissions of nitrogen oxides.
Council Directive 92/42/EEC is repealed, except for Articles 7(2) and 8 thereof and Annexes III to V thereto, without prejudice to the obligations of the Member States relating to the transposition into national law and application of that Directive until the ecodesign requirements set out in Annex II of this Regulation start to apply.
This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union.
This Regulation shall be binding in its entirety and directly applicable in all Member States.
Done at Brussels, 2 August 2013.
For the Commission
The President
José Manuel Barroso
For the purposes of Annexes II to V the following definitions shall apply:
for fuel boiler space heaters and fuel boiler combination heaters, a weighted average of the useful efficiency at rated heat output and the useful efficiency at 30 % of the rated heat output, expressed in %;
for electric boiler space heaters and electric boiler combination heaters, the useful efficiency at rated heat output, expressed in %;
for cogeneration space heaters not equipped with supplementary heaters, the useful efficiency at rated heat output, expressed in %;
for cogeneration space heaters equipped with supplementary heaters, a weighted average of the useful efficiency at rated heat output with supplementary heater disabled, and the useful efficiency at rated heat output with supplementary heater enabled, expressed in %;
From 26 September 2015 the seasonal space heating energy efficiency and useful efficiencies of heaters shall not fall below the following values:
Fuel boiler space heaters with rated heat output ≤ 70 kW and fuel boiler combination heaters with rated heat output ≤ 70 kW, with the exception of type B1 boilers with rated heat output ≤ 10 kW and type B1 combination boilers with rated heat output ≤ 30 kW:
The seasonal space heating energy efficiency shall not fall below 86 %.
Type B1 boilers with rated heat output ≤ 10 kW and type B1 combination boilers with rated heat output ≤ 30 kW:
The seasonal space heating energy efficiency shall not fall below 75 %.
Fuel boiler space heaters with rated heat output > 70 kW and ≤ 400 kW and fuel boiler combination heaters with rated heat output > 70 kW and ≤ 400 kW:
The useful efficiency at 100 % of the rated heat output shall not fall below 86 %, and the useful efficiency at 30 % of the rated heat output shall not fall below 94 %.
Electric boiler space heaters and electric boiler combination heaters:
The seasonal space heating energy efficiency shall not fall below 30 %.
Cogeneration space heaters:
The seasonal space heating energy efficiency shall not fall below 86 %.
Heat pump space heaters and heat pump combination heaters, with the exception of low-temperature heat pumps:
The seasonal space heating energy efficiency shall not fall below 100 %.
Low-temperature heat pumps:
The seasonal space heating energy efficiency shall not fall below 115 %.
From 26 September 2017 the seasonal space heating energy efficiency of electric boiler space heaters, electric boiler combination heaters, cogeneration space heaters, heat pump space heaters and heat pump combination heaters shall not fall below the following values:
Electric boiler space heaters and electric boiler combination heaters:
The seasonal space heating energy efficiency shall not fall below 36 %.
Cogeneration space heaters:
The seasonal space heating energy efficiency shall not fall below 100 %.
Heat pump space heaters and heat pump combination heaters, with the exception of low-temperature heat pumps:
The seasonal space heating energy efficiency shall not fall below 110 %.
Low-temperature heat pumps:
The seasonal space heating energy efficiency shall not fall below 125 %.
Declared load profile | 3XS | XXS | XS | S | M | L | XL | XXL | 3XL | 4XL |
---|---|---|---|---|---|---|---|---|---|---|
Water heating energy efficiency | 22 % | 23 % | 26 % | 26 % | 30 % | 30 % | 30 % | 32 % | 32 % | 32 % |
Declared load profile | 3XS | XXS | XS | S | M | L | XL | XXL | 3XL | 4XL |
---|---|---|---|---|---|---|---|---|---|---|
Water heating energy efficiency | 32 % | 32 % | 32 % | 32 % | 36 % | 37 % | 38 % | 60 % | 64 % | 64 % |
From 26 September 2015 the sound power level of heat pump space heaters and heat pump combination heaters shall not exceed the following values:
Rated heat output ≤ 6 kW | Rated heat output > 6 kW and ≤ 12 kW | Rated heat output > 12 kW and ≤ 30 kW | Rated heat output > 30 kW and ≤ 70 kW | ||||
---|---|---|---|---|---|---|---|
Sound power level (LWA ), indoors | Sound power level (LWA ), outdoors | Sound power level (LWA ), indoors | Sound power level (LWA ), outdoors | Sound power level (LWA ), indoors | Sound power level (LWA ), outdoors | Sound power level (LWA ), indoors | Sound power level (LWA ), outdoors |
60 dB | 65 dB | 65 dB | 70 dB | 70 dB | 78 dB | 80 dB | 88 dB |
fuel boiler space heaters and fuel boiler combination heaters using gaseous fuels: 56 mg/kWh fuel input in terms of GCV;
fuel boiler space heaters and fuel boiler combination heaters using liquid fuels: 120 mg/kWh fuel input in terms of GCV;
cogeneration space heaters equipped with external combustion using gaseous fuels: 70 mg/kWh fuel input in terms of GCV;
cogeneration space heaters equipped with external combustion using liquid fuels: 120 mg/kWh fuel input in terms of GCV;
cogeneration space heaters equipped with an internal combustion engine using gaseous fuels: 240 mg/kWh fuel input in terms of GCV;
cogeneration space heaters equipped with an internal combustion engine using liquid fuels: 420 mg/kWh fuel input in terms of GCV;
heat pump space heaters and heat pump combination heaters equipped with external combustion using gaseous fuels: 70 mg/kWh fuel input in terms of GCV;
heat pump space heaters and heat pump combination heaters equipped with external combustion using liquid fuels: 120 mg/kWh fuel input in terms of GCV;
heat pump space heaters and heat pump combination heaters equipped with an internal combustion engine using gaseous fuels: 240 mg/kWh fuel input in terms of GCV;
heat pump space heaters and heat pump combination heaters equipped with an internal combustion engine using liquid fuels: 420 mg/kWh fuel input in terms of GCV.
From 26 September 2015 the following product information on heaters shall be provided:
the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers shall contain the following elements:
for boiler space heaters, boiler combination heaters and cogeneration space heaters, the technical parameters set out in Table 1, measured and calculated in accordance with Annex III;
for heat pump space heaters and heat pump combination heaters, the technical parameters set out in Table 2, measured and calculated in accordance with Annex III;
any specific precautions that shall be taken when the heater is assembled, installed or maintained;
for type B1 boilers and type B1 combination boilers, their characteristics and the following standard text: ‘This natural draught boiler is intended to be connected only to a flue shared between multiple dwellings in existing buildings that evacuates the residues of combustion to the outside of the room containing the boiler. It draws the combustion air directly from the room and incorporates a draught diverter. Due to lower efficiency, any other use of this boiler shall be avoided and would result in higher energy consumption and higher operating costs.’;
for heat generators designed for heaters, and heater housings to be equipped with such heat generators, their characteristics, the requirements for assembly, to ensure compliance with the ecodesign requirements for heaters and, where appropriate, the list of combinations recommended by the manufacturer;
information relevant for disassembly, recycling and/or disposal at end-of-life;
the technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:
the elements specified in point (a);
for heat pump space heaters and heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;
the following information shall be durably marked on the heater:
if applicable, ‘type B1 boiler’ or ‘type B1 combination boiler’;
for cogeneration space heaters, the electrical capacity.
Information requirements for boiler space heaters, boiler combination heaters and cogeneration space heaters
a High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet. | ||||||||
b Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet). | ||||||||
Model(s): [information identifying the model(s) to which the information relates] | ||||||||
Condensing boiler: [yes/no] | ||||||||
Low-temperatureb boiler: [yes/no] | ||||||||
B1 boiler: [yes/no] | ||||||||
Cogeneration space heater: [yes/no] | If yes, equipped with a supplementary heater: [yes/no] | |||||||
Combination heater: [yes/no] | ||||||||
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
---|---|---|---|---|---|---|---|---|
Rated heat output | Prated | x | kW | Seasonal space heating energy efficiency | ηs | x | % | |
For boiler space heaters and boiler combination heaters: Useful heat output | For boiler space heaters and boiler combination heaters: Useful efficiency | |||||||
At rated heat output and high-temperature regimea | P4 | x,x | kW | At rated heat output and high-temperature regimea | η4 | x,x | % | |
At 30 % of rated heat output and low-temperature regimeb | P1 | x,x | kW | At 30 % of rated heat output and low-temperature regimeb | η1 | x,x | % | |
For cogeneration space heaters: Useful heat output | For cogeneration space heaters: Useful efficiency | |||||||
At rated heat output of cogeneration space heater with supplementary heater disabled | PCHP100 + Sup0 | x,x | kW | At rated heat output of cogeneration space heater with supplementary heater disabled | ηCHP100 + Sup0 | x,x | % | |
At rated heat output of cogeneration space heater with supplementary heater enabled | PCHP100 + Sup100 | x,x | kW | At rated heat output of cogeneration space heater with supplementary heater enabled | ηCHP100 + Sup100 | x,x | % | |
For cogeneration space heaters: Electrical efficiency | Supplementary heater | |||||||
At rated heat output of cogeneration space heater with supplementary heater disabled | ηel,CHP100 + Sup0 | x,x | % | Rated heat output | Psup | x,x | kW | |
At rated heat output of cogeneration space heater with supplementary heater enabled | ηel,CHP100 + Sup100 | x,x | % | Type of energy input | ||||
Auxiliary electricity consumption | Other items | |||||||
At full load | elmax | x,xxx | kW | Standby heat loss | Pstby | x,xxx | kW | |
At part load | elmin | x,xxx | kW | Ignition burner power consumption | Pign | x,xxx | kW | |
In standby mode | PSB | x,xxx | kW | Emissions of nitrogen oxides | NOx | x | mg/kWh | |
For combination heaters: | ||||||||
Declared load profile | Water heating energy efficiency | ηwh | x | % | ||||
Daily electricity consumption | Qelec | x,xxx | kWh | Daily fuel consumption | Qfuel | x,xxx | kWh | |
Contact details | Name and address of the manufacturer or its authorised representative. |
Information requirements for heat pump space heaters and heat pump combination heaters
a For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). | ||||||||
b If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9. | ||||||||
Model(s): [information identifying the model(s) to which the information relates] | ||||||||
Air-to-water heat pump: [yes/no] | ||||||||
Water-to-water heat pump: [yes/no] | ||||||||
Brine-to-water heat pump: [yes/no] | ||||||||
Low-temperature heat pump: [yes/no] | ||||||||
Equipped with a supplementary heater: [yes/no] | ||||||||
Heat pump combination heater: [yes/no] | ||||||||
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application. | ||||||||
Parameters shall be declared for average climate conditions. | ||||||||
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
---|---|---|---|---|---|---|---|---|
Rated heat output a | Prated | x | kW | Seasonal space heating energy efficiency | ηs | x | % | |
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj | Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj | |||||||
Tj = – 7 °C | Pdh | x,x | kW | Tj = – 7 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = + 2 °C | Pdh | x,x | kW | Tj = + 2 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = + 7 °C | Pdh | x,x | kW | Tj = + 7 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = + 12 °C | Pdh | x,x | kW | Tj = + 12 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = bivalent temperature | Pdh | x,x | kW | Tj = bivalent temperature | COPd or PERd | x,xx or x,x | – or % | |
Tj = operation limit temperature | Pdh | x,x | kW | Tj = operation limit temperature | COPd or PERd | x,xx or x,x | – or % | |
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | Pdh | x,x | kW | For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | COPd or PERd | x,xx or x,x | – or % | |
Bivalent temperature | Tbiv | x | °C | For air-to-water heat pumps: Operation limit temperature | TOL | x | °C | |
Cycling interval capacity for heating | Pcych | x,x | kW | Cycling interval efficiency | COPcyc or PERcyc | x,xx or x,x | – or % | |
Degradation co-efficientb | Cdh | x,x | — | Heating water operating limit temperature | WTOL | x | °C | |
Power consumption in modes other than active mode | Supplementary heater | |||||||
Off mode | POFF | x,xxx | kW | Rated heat outputa | Psup | x,x | kW | |
Thermostat-off mode | PTO | x,xxx | kW | |||||
Standby mode | PSB | x,xxx | kW | Type of energy input | ||||
Crankcase heater mode | PCK | x,xxx | kW | |||||
Other items | ||||||||
Capacity control | fixed/variable | For air-to-water heat pumps: Rated air flow rate, outdoors | — | x | m3/h | |||
Sound power level, indoors/outdoors | LWA | x/x | dB | For water-/brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger | — | x | m3/h | |
Emissions of nitrogen oxides | NOx | x | mg/kWh | |||||
For heat pump combination heater: | ||||||||
Declared load profile | x | Water heating energy efficiency | ηwh | x | % | |||
Daily electricity consumption | Qelec | x,xxx | kWh | Daily fuel consumption | Qfuel | x,xxx | kWh | |
Contact details | Name and address of the manufacturer or its authorised representative. |
For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall be made using harmonised standards the reference numbers of which have been published for this purpose in the Official Journal of the European Union, or using other reliable, accurate and reproducible methods that take into account the generally recognised state-of-the-art methods. They shall meet the conditions and technical parameters set out in points 2 to 5.
General conditions for measurements and calculations
For the purposes of the measurements set out in points 2 to 5, the indoor ambient temperature shall be set at 20 °C ± 1 °C.
For the purposes of the calculations set out in points 3 to 5, consumption of electricity shall be multiplied by a conversion coefficient CC of 2,5.
Emissions of nitrogen oxides shall be measured as the sum of nitrogen monoxide and nitrogen dioxide, and expressed in nitrogen dioxide.
For heaters equipped with supplementary heaters, the measurement and calculation of rated heat output, seasonal space heating energy efficiency, water heating energy efficiency, sound power level and emissions of nitrogen oxides shall take account of the supplementary heater.
Declared values for rated heat output, seasonal space heating energy efficiency, water heating energy efficiency, sound power level and emissions of nitrogen oxides shall be rounded to the nearest integer.
Any heat generator designed for a heater, and any heater housing to be equipped with such a heat generator, shall be tested with an appropriate heater housing and heat generator, respectively.
Seasonal space heating energy efficiency of boiler space heaters, boiler combination heaters and cogeneration space heaters
The seasonal space heating energy efficiency ηs shall be calculated as the seasonal space heating energy efficiency in active mode ηson , corrected by contributions accounting for temperature controls, auxiliary electricity consumption, standby heat loss, ignition burner power consumption (if applicable) and, for cogeneration space heaters, corrected by adding the electrical efficiency multiplied by a conversion coefficient CC of 2,5.
Seasonal space heating energy efficiency of heat pump space heaters and heat pump combination heaters
For establishing the rated coefficient of performance COPrated or rated primary energy ratio PERrated , the sound power level or emissions of nitrogen oxides, the operating conditions shall be the standard rating conditions set out in Table 3 and the same declared capacity for heating shall be used.
The active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon shall be calculated on the basis of the part load for heating Ph(Tj), the supplementary capacity for heating sup(Tj) (if applicable) and the bin-specific coefficient of performance COPbin(Tj) or bin-specific primary energy ratio PERbin(Tj), weighted by the bin-hours for which the bin conditions apply, using the following conditions:
the reference design conditions set out in Table 4;
the European reference heating season under average climate conditions set out in Table 5;
if applicable, the effects of any degradation of energy efficiency caused by cycling depending on the type of control of the heating capacity.
The reference annual heat demand QH shall be the design load for heating Pdesignh multiplied by the annual equivalent active mode hours HHE of 2 066.
The annual energy consumption QHE shall be calculated as the sum of:
the ratio of the reference annual heating demand QH and the active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon and
the energy consumption for off, thermostat-off, standby, and crankcase heater mode during the heating season.
The seasonal coefficient of performance SCOP or seasonal primary energy ratio SPER shall be calculated as the ratio of the reference annual heat demand QH and the annual energy consumption QHE .
The seasonal space heating energy efficiency ηs shall be calculated as the seasonal coefficient of performance SCOP divided by the conversion coefficient CC or the seasonal primary energy ratio SPER, corrected by contributions accounting for temperature controls and, for water-/brine-to-water heat pump space heaters and heat pump combination heaters, the electricity consumption of one or more ground water pumps.
Water heating energy efficiency of combination heaters
The water heating energy efficiency ηwh of a combination heater shall be calculated as the ratio between the reference energy Qref of the declared load profile and the energy required for its generation under the following conditions:
measurements shall be carried out using the load profiles set out in Table 7;
measurements shall be carried out using a 24-hour measurement cycle as follows:
00:00 to 06:59: no water draw-off;
from 07:00: water draw-offs according to the declared load profile;
from end of last water draw-off until 24:00: no water draw-off;
the declared load profile shall be the maximum load profile or the load profile one below the maximum load profile;
for heat pump combination heaters, the following additional conditions apply:
heat pump combination heaters shall be tested under the conditions set out in Table 3;
heat pump combination heaters which use ventilation exhaust air as the heat source shall be tested under the conditions set out in Table 6.
Standard rating conditions for heat pump space heaters and heat pump combination heaters
Heat source | Outdoor heat exchanger | Indoor heat exchanger | |||
---|---|---|---|---|---|
Inlet dry bulb (wet bulb) temperature | Heat pump space heaters and heat pump combination heaters, except low-temperature heat pumps | Low-temperature heat pumps | |||
Inlet temperature | Outlet temperature | Inlet temperature | Outlet temperature | ||
Outdoor air | + 7 °C (+ 6 °C) | + 47 °C | + 55 °C | + 30 °C | + 35 °C |
Exhaust air | + 20 °C (+ 12 °C) | ||||
Inlet/outlet temperature | |||||
Water | + 10 °C/+ 7 °C | ||||
Brine | 0 °C/– 3 °C |
Reference design conditions for heat pump space heaters and heat pump combination heaters, temperatures in dry bulb air temperature (wet bulb air temperature indicated in brackets)
Reference design temperature | Bivalent temperature | Operation limit temperature |
---|---|---|
Tdesignh | Tbiv | TOL |
– 10 (– 11) °C | maximum + 2 °C | maximum – 7 °C |
European reference heating season under average climate conditions for heat pump space heaters and heat pump combination heaters
binj | Tj [°C] | Hj [h/annum] |
---|---|---|
1 to 20 | – 30 to – 11 | 0 |
21 | -10 | 1 |
22 | -9 | 25 |
23 | -8 | 23 |
24 | -7 | 24 |
25 | -6 | 27 |
26 | -5 | 68 |
27 | -4 | 91 |
28 | -3 | 89 |
29 | -2 | 165 |
30 | -1 | 173 |
31 | 0 | 240 |
32 | 1 | 280 |
33 | 2 | 320 |
34 | 3 | 357 |
35 | 4 | 356 |
36 | 5 | 303 |
37 | 6 | 330 |
38 | 7 | 326 |
39 | 8 | 348 |
40 | 9 | 335 |
41 | 10 | 315 |
42 | 11 | 215 |
43 | 12 | 169 |
44 | 13 | 151 |
45 | 14 | 105 |
46 | 15 | 74 |
Total hours: | 4 910 |
Maximum ventilation exhaust air available [m3/h], at humidity of 5,5 g/m3
Declared load profile | XXS | XS | S | M | L | XL | XXL | 3XL | 4XL |
---|---|---|---|---|---|---|---|---|---|
Maximum ventilation exhaust air available | 109 | 128 | 128 | 159 | 190 | 870 | 1 021 | 2 943 | 8 830 |
Water heating load profiles of combination heaters
h | 3XS | XXS | XS | S | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Q tap | f | Tm | Q tap | f | Tm | Q tap | f | Tm | Q tap | f | Tm | Tp | |
kWh | l/min | °C | kWh | l/min | °C | kWh | l/min | °C | kWh | l/min | °C | °C | |
07:00 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | 0,105 | 3 | 25 | ||||
07:05 | 0,015 | 2 | 25 | ||||||||||
07:15 | 0,015 | 2 | 25 | ||||||||||
07:26 | 0,015 | 2 | 25 | ||||||||||
07:30 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | 0,525 | 3 | 35 | 0,105 | 3 | 25 | |
07:45 | |||||||||||||
08:01 | |||||||||||||
08:05 | |||||||||||||
08:15 | |||||||||||||
08:25 | |||||||||||||
08:30 | 0,105 | 2 | 25 | 0,105 | 3 | 25 | |||||||
08:45 | |||||||||||||
09:00 | 0,105 | 2 | 25 | ||||||||||
09:30 | 0,105 | 2 | 25 | 0,105 | 2 | 25 | 0,105 | 3 | 25 | ||||
10:00 | |||||||||||||
10:30 | |||||||||||||
11:00 | |||||||||||||
11:30 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | 0,105 | 3 | 25 | ||||
11:45 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | 0,105 | 3 | 25 | ||||
12:00 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
12:30 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
12:45 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | 0,525 | 3 | 35 | 0,315 | 4 | 10 | 55 |
14:30 | 0,015 | 2 | 25 | ||||||||||
15:00 | 0,015 | 2 | 25 | ||||||||||
15:30 | 0,015 | 2 | 25 | ||||||||||
16:00 | 0,015 | 2 | 25 | ||||||||||
16:30 | |||||||||||||
17:00 | |||||||||||||
18:00 | 0,105 | 2 | 25 | 0,105 | 3 | 25 | |||||||
18:15 | 0,105 | 2 | 25 | 0,105 | 3 | 40 | |||||||
18:30 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
19:00 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
19:30 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
20:00 | 0,105 | 2 | 25 | ||||||||||
20:30 | 1,05 | 3 | 35 | 0,42 | 4 | 10 | 55 | ||||||
20:45 | 0,105 | 2 | 25 | ||||||||||
20:46 | |||||||||||||
21:00 | 0,105 | 2 | 25 | ||||||||||
21:15 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
21:30 | 0,015 | 2 | 25 | 0,525 | 5 | 45 | |||||||
21:35 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
21:45 | 0,015 | 2 | 25 | 0,105 | 2 | 25 | |||||||
Qref | 0,345 | 2,1 | 2,1 | 2,1 |
h | M | L | XL | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Q tap | f | Tm | Tp | Q tap | f | Tm | Tp | Q tap | f | Tm | Tp | |
kWh | l/min | °C | °C | kWh | l/min | °C | °C | kWh | l/min | °C | °C | |
07:00 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
07:05 | 1,4 | 6 | 40 | 1,4 | 6 | 40 | ||||||
07:15 | 1,82 | 6 | 40 | |||||||||
07:26 | 0,105 | 3 | 25 | |||||||||
07:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | ||||||
07:45 | 0,105 | 3 | 25 | 4,42 | 10 | 10 | 40 | |||||
08:01 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | ||||||
08:05 | 3,605 | 10 | 10 | 40 | ||||||||
08:15 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | ||||||
08:25 | 0,105 | 3 | 25 | |||||||||
08:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
08:45 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
09:00 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
09:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
10:00 | 0,105 | 3 | 25 | |||||||||
10:30 | 0,105 | 3 | 10 | 40 | 0,105 | 3 | 10 | 40 | 0,105 | 3 | 10 | 40 |
11:00 | 0,105 | 3 | 25 | |||||||||
11:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
11:45 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
12:00 | ||||||||||||
12:30 | ||||||||||||
12:45 | 0,315 | 4 | 10 | 55 | 0,315 | 4 | 10 | 55 | 0,735 | 4 | 10 | 55 |
14:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
15:00 | 0,105 | 3 | 25 | |||||||||
15:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
16:00 | 0,105 | 3 | 25 | |||||||||
16:30 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
17:00 | 0,105 | 3 | 25 | |||||||||
18:00 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
18:15 | 0,105 | 3 | 40 | 0,105 | 3 | 40 | 0,105 | 3 | 40 | |||
18:30 | 0,105 | 3 | 40 | 0,105 | 3 | 40 | 0,105 | 3 | 40 | |||
19:00 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | |||
19:30 | ||||||||||||
20:00 | ||||||||||||
20:30 | 0,735 | 4 | 10 | 55 | 0,735 | 4 | 10 | 55 | 0,735 | 4 | 10 | 55 |
20:45 | ||||||||||||
20:46 | 4,42 | 10 | 10 | 40 | ||||||||
21:00 | 3,605 | 10 | 10 | 40 | ||||||||
21:15 | 0,105 | 3 | 25 | 0,105 | 3 | 25 | ||||||
21:30 | 1,4 | 6 | 40 | 0,105 | 3 | 25 | 4,42 | 10 | 10 | 40 | ||
21:35 | ||||||||||||
21:45 | ||||||||||||
Qref | 5,845 | 11,655 | 19,07 |
h | XXL | 3XL | 4XL | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Q tap | f | Tm | Tp | Q tap | f | Tm | Tp | Q tap | f | Tm | Tp | |
kWh | l/min | °C | °C | kWh | l/min | °C | °C | kWh | l/min | °C | °C | |
07:00 | 0,105 | 3 | 25 | 11,2 | 48 | 40 | 22,4 | 96 | 40 | |||
07:05 | ||||||||||||
07:15 | 1,82 | 6 | 40 | |||||||||
07:26 | 0,105 | 3 | 25 | |||||||||
07:30 | ||||||||||||
07:45 | 6,24 | 16 | 10 | 40 | ||||||||
08:01 | 0,105 | 3 | 25 | 5,04 | 24 | 25 | 10,08 | 48 | 25 | |||
08:05 | ||||||||||||
08:15 | 0,105 | 3 | 25 | |||||||||
08:25 | ||||||||||||
08:30 | 0,105 | 3 | 25 | |||||||||
08:45 | 0,105 | 3 | 25 | |||||||||
09:00 | 0,105 | 3 | 25 | 1,68 | 24 | 25 | 3,36 | 48 | 25 | |||
09:30 | 0,105 | 3 | 25 | |||||||||
10:00 | 0,105 | 3 | 25 | |||||||||
10:30 | 0,105 | 3 | 10 | 40 | 0,84 | 24 | 10 | 40 | 1,68 | 48 | 10 | 40 |
11:00 | 0,105 | 3 | 25 | |||||||||
11:30 | 0,105 | 3 | 25 | |||||||||
11:45 | 0,105 | 3 | 25 | 1,68 | 24 | 25 | 3,36 | 48 | 25 | |||
12:00 | ||||||||||||
12:30 | ||||||||||||
12:45 | 0,735 | 4 | 10 | 55 | 2,52 | 32 | 10 | 55 | 5,04 | 64 | 10 | 55 |
14:30 | 0,105 | 3 | 25 | |||||||||
15:00 | 0,105 | 3 | 25 | |||||||||
15:30 | 0,105 | 3 | 25 | 2,52 | 24 | 25 | 5,04 | 48 | 25 | |||
16:00 | 0,105 | 3 | 25 | |||||||||
16:30 | 0,105 | 3 | 25 | |||||||||
17:00 | 0,105 | 3 | 25 | |||||||||
18:00 | 0,105 | 3 | 25 | |||||||||
18:15 | 0,105 | 3 | 40 | |||||||||
18:30 | 0,105 | 3 | 40 | 3,36 | 24 | 25 | 6,72 | 48 | 25 | |||
19:00 | 0,105 | 3 | 25 | |||||||||
19:30 | ||||||||||||
20:00 | ||||||||||||
20:30 | 0,735 | 4 | 10 | 55 | 5,88 | 32 | 10 | 55 | 11,76 | 64 | 10 | 55 |
20:45 | ||||||||||||
20:46 | 6,24 | 16 | 10 | 40 | ||||||||
21:00 | ||||||||||||
21:15 | 0,105 | 3 | 25 | |||||||||
21:30 | 6,24 | 16 | 10 | 40 | 12,04 | 48 | 40 | 24,08 | 96 | 40 | ||
21:35 | ||||||||||||
21:45 | ||||||||||||
Qref | 24,53 | 46,76 | 93,52 |
When performing the market surveillance checks referred to in Article 3(2) of Directive 2009/125/EC, the authorities of the Member States shall apply the following verification procedure for the requirements set out in Annex II:
The Member State authorities shall test one single unit per model.
The heater model shall be considered to comply with the applicable requirements set out in Annex II to this Regulation if:
the declared values comply with the requirements set out in Annex II;
the seasonal space heating energy efficiency ηs is not more than 8 % lower than the declared value at the rated heat output of the unit;
the water heating energy efficiency ηwh is not more than 8 % lower than the declared value at the rated heat output of the unit;
the sound power level LWA is not more than 2 dB higher than the declared value of the unit; and
the emissions of nitrogen oxides, expressed in nitrogen dioxide, are not more than 20 % higher than the declared value of the unit.
If the result referred to in point 2(a) is not achieved, the model and all other equivalent models shall be considered not to comply with this Regulation. If the result referred to in point 2(b) to (e) is not achieved, the Member State authorities shall randomly select three additional units of the same model for testing.
The heater model shall be considered to comply with the applicable requirements set out in Annex II to this Regulation if:
the declared values of each of the three units comply with the requirements set out in Annex II;
the average of the three units for seasonal space heating energy efficiency ηs is not more than 8 % lower than the declared value at the rated heat output of the unit;
the average of the three units for water heating energy efficiency ηwh is not more than 8 % lower than the declared value at the rated heat output of the unit;
the average of the three units for the sound power level LWA is not more than 2 dB higher than the declared value of the unit; and
the average of the three units for emissions of nitrogen oxides, expressed in nitrogen dioxide, are not more than 20 % higher than the declared value of the unit.
If the results referred to in point 4 are not achieved, the model and all other equivalent models shall be considered not to comply with this Regulation. The Member State authorities shall provide the test results and other relevant information to the authorities of the other Member States and to the Commission within one month of the decision being taken on the non-compliance of the model.
Member State authorities shall use the measurement and calculation methods set out in Annex III.
At the time of entry into force of this Regulation, the best available technology on the market for heaters in terms of seasonal space heating energy efficiency, water heating energy efficiency, sound power level and emissions of nitrogen oxides was identified as follows:
Benchmark for seasonal space heating energy efficiency in medium-temperature application: 145 %;
Benchmarks for water heating energy efficiency of combination heaters:
Declared load profile | 3XS | XXS | XS | S | M | L | XL | XXL | 3XL | 4XL |
---|---|---|---|---|---|---|---|---|---|---|
Water heating energy efficiency | 35 % | 35 % | 38 % | 38 % | 75 % | 110 % | 115 % | 120 % | 130 % | 130 % |
Benchmarks for sound power level (LWA ), outdoor, of heat pump space heaters and of heat pump combination heaters with rated heat output:
≤ 6 kW: 39 dB;
> 6 kW and ≤ 12 kW: 40 dB;
> 12 kW and ≤ 30 kW: 41 dB;
> 30 kW and ≤ 70 kW: 67 dB.
Benchmarks for emissions of nitrogen oxides, expressed in nitrogen dioxide:
of boiler space heaters and boiler combination heaters using gaseous fuels: 14 mg/kWh fuel input in terms of GCV;
of boiler space heaters and boiler combination heaters using liquid fuels: 50 mg/kWh fuel input in terms of GCV.
The benchmarks specified in points 1 to 4 do not necessarily imply that a combination of these values is achievable for a single heater.
See page 1 of this Official Journal.
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including:
The data on this page is available in the alternative data formats listed: