2. The fuel oil storage area shall be surrounded by a bund capable of retaining within the area–
(a)in a case where all the fuel oil within the storage area is contained in one fuel storage tank, a volume of fuel oil not less than 110 per cent of the capacity of the tank;
(b)in a case where all the fuel oil within the storage area is contained in more than one fuel storage tank, a volume of fuel oil not less than whichever is the greater of–
(i)110 per cent of the capacity of the largest tank within the storage area; and
(ii)25 per cent of the total volume of such oil which could be stored in tanks within the area; and
(c)in any other case, a volume of fuel oil not less than whichever is the greater of–
(i)110 per cent of the capacity of the largest container within the storage area; and
(ii)25 per cent of the total volume of such oil at any time stored within the area.
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made): The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: