European seasonal conditions, as defined in Table 1 of this Annex;
Reference design conditions, as defined in Table 3 of this Annex;
Electric energy consumption for all relevant modes of operation, using time periods as defined in Table 4 of this Annex;
Effects of the degradation of the energy efficiency caused by on/off cycling (if applicable) depending on the type of control of the cooling and/or heating capacity;
Corrections on the seasonal coefficients of performance in conditions where the heating load can not be met by the heating capacity;
The contribution of a back-up heater (if applicable) in the calculation of the seasonal efficiency of a unit in heating mode.
Bin number (j), outdoor temperature (Tj) in °C and number of hours per bin (hj) for the cooling season and for heating seasons ‘average’, ‘warmer’ and ‘colder’. ‘db’ = dry bulb temperature
COOLING SEASON | HEATING SEASON | |||||||
---|---|---|---|---|---|---|---|---|
Average | Warmer | Colder | ||||||
j# | Tj°C | hjh | j# | Tj°C | hjAh | hj Wh | hjCh | |
db | db | |||||||
1 | 17 | 205 | 1 to 8 | – 30 to – 23 | 0 | 0 | 0 | |
2 | 18 | 227 | 9 | -22 | 0 | 0 | 1 | |
3 | 19 | 225 | 10 | -21 | 0 | 0 | 6 | |
4 | 20 | 225 | 11 | -20 | 0 | 0 | 13 | |
5 | 21 | 216 | 12 | -19 | 0 | 0 | 17 | |
6 | 22 | 215 | 13 | -18 | 0 | 0 | 19 | |
7 | 23 | 218 | 14 | -17 | 0 | 0 | 26 | |
8 | 24 | 197 | 15 | -16 | 0 | 0 | 39 | |
9 | 25 | 178 | 16 | -15 | 0 | 0 | 41 | |
10 | 26 | 158 | 17 | -14 | 0 | 0 | 35 | |
11 | 27 | 137 | 18 | -13 | 0 | 0 | 52 | |
12 | 28 | 109 | 19 | -12 | 0 | 0 | 37 | |
13 | 29 | 88 | 20 | -11 | 0 | 0 | 41 | |
14 | 30 | 63 | 21 | -10 | 1 | 0 | 43 | |
15 | 31 | 39 | 22 | -9 | 25 | 0 | 54 | |
16 | 32 | 31 | 23 | -8 | 23 | 0 | 90 | |
17 | 33 | 24 | 24 | -7 | 24 | 0 | 125 | |
18 | 34 | 17 | 25 | -6 | 27 | 0 | 169 | |
19 | 35 | 13 | 26 | -5 | 68 | 0 | 195 | |
20 | 36 | 9 | 27 | -4 | 91 | 0 | 278 | |
21 | 37 | 4 | 28 | -3 | 89 | 0 | 306 | |
22 | 38 | 3 | 29 | -2 | 165 | 0 | 454 | |
23 | 39 | 1 | 30 | -1 | 173 | 0 | 385 | |
24 | 40 | 0 | 31 | 0 | 240 | 0 | 490 | |
32 | 1 | 280 | 0 | 533 | ||||
33 | 2 | 320 | 3 | 380 | ||||
34 | 3 | 357 | 22 | 228 | ||||
35 | 4 | 356 | 63 | 261 | ||||
36 | 5 | 303 | 63 | 279 | ||||
37 | 6 | 330 | 175 | 229 | ||||
38 | 7 | 326 | 162 | 269 | ||||
39 | 8 | 348 | 259 | 233 | ||||
40 | 9 | 335 | 360 | 230 | ||||
41 | 10 | 315 | 428 | 243 | ||||
42 | 11 | 215 | 430 | 191 | ||||
43 | 12 | 169 | 503 | 146 | ||||
44 | 13 | 151 | 444 | 150 | ||||
45 | 14 | 105 | 384 | 97 | ||||
46 | 15 | 74 | 294 | 61 | ||||
Total | 2 602 | 4 910 | 3 590 | 6 446 |
Standard rating conditions, temperatures in ‘dry bulb’ air temperature (‘wet bulb’ indicated in brackets)
a In case of single ducts, the condensor (evaporator) when cooling (heating), is not supplied with outdoor air, but indoor air. | |||
Appliance | Function | Indoor air temperature(°C) | Outdoor air temperature(°C) |
---|---|---|---|
air conditioners, excluding single duct | cooling | 27 (19) | 35 (24) |
heating | 20 (max. 15) | 7(6) | |
single duct | cooling | 35 (24) | 35 (24)a |
heating | 20 (12) | 20 (12)a |
Reference design conditions, temperatures in ‘dry bulb’ air temperature (‘wet bulb’ indicated in brackets)
Function / season | Indoor air temperature(°C) | Outdoor air temperature(°C) | Bivalent temperature(°C) | Operating limit temperature(°C) |
---|---|---|---|---|
Tin | Tdesignc/Tdesignh | Tbiv | Tol | |
cooling | 27 (19) | Tdesignc = 35 (24) | n.a. | n.a. |
heating / Average | 20 (15) | Tdesignh = – 10 (– 11) | max. 2 | max. – 7 |
heating / Warmer | Tdesignh = 2 (1) | max. 7 | max. 2 | |
heating / Colder | Tdesignh = – 22 (– 23) | max. – 7 | max. – 15 |
Operational hours per type of appliance per functional mode to be used for calculation of electricity consumption
Type of appliance / functionality (if applicable) | Unit | Heating season | On mode | Thermostat-off mode | Standby mode | Off mode | Crankcase heater mode | |
---|---|---|---|---|---|---|---|---|
cooling: HCEheating: HHE | HTO | HSB | HOFF | HCK | ||||
Air conditioners, except double ducts and single duct | ||||||||
Cooling mode, if appliance offers cooling only | h/annum | 350 | 221 | 2 142 | 5 088 | 7 760 | ||
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/annum | 350 | 221 | 2 142 | 0 | 2 672 | |
Heating mode | h/annum | Average | 1 400 | 179 | 0 | 0 | 179 | |
Warmer | 1 400 | 755 | 0 | 0 | 755 | |||
Colder | 2 100 | 131 | 0 | 0 | 131 | |||
Heating mode, if appliance offers heating only | h/annum | Average | 1 400 | 179 | 0 | 3 672 | 3 851 | |
Warmer | 1 400 | 755 | 0 | 4 345 | 4 476 | |||
Colder | 2 100 | 131 | 0 | 2 189 | 2 944 | |||
Double duct air conditioner | cooling: HCEheating: HHE | HTO | HSB | HOFF | HCK | |||
Cooling mode, if appliance offers cooling only | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/60 min | 1 | n/a | n/a | n/a | n/a | |
Heating mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Heating mode, if appliance offers heating only | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Single duct air conditioner | cooling: HCEheating: HHE | |||||||
Cooling mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Heating mode | h/60 min | 1 | n/a | n/a | n/a | n/a |
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: