5. For paragraph (2) of that regulation there shall be substituted the following paragraph—
“(2) For the purposes of this regulation, unless otherwise agreed by the consumer, the permitted variations are:
(a)a variation not exceeding one per cent above or below the declared frequency;
(b)in the case of a low voltage supply, a variation not exceeding ten per cent above or six per cent below the declared voltage at the declared frequency;
(c)in the case of a high voltage supply operating at a voltage below 132 kV, a variation not exceeding six per cent above or below the declared voltage at the declared frequency; and
(d)in the case of a high voltage supply operating at a voltage of 132 kV or above, a variation not exceeding ten per cent above or below the declared voltage at the declared frequency.”