1.  The energy efficiency class of a regulated appliance shall be determined in accordance with the following tables. The energy efficiency ratio (EER) shall be determined in accordance with the test procedures of the harmonised standard at conditions T1 ‘moderate’.

Table 1 Air-cooled air conditioners

Table 1.1
Energy Efficiency classSplit and multi-split appliances
A3.20<EER
B3.20≥EER>3.00
C3.00≥EER>2.80
D2.80≥EER>2.60
E2.60≥EER>2.40
F2.40≥EER>2.20
G2.20≥EER
Table 1.2
Energy Efficiency classPackaged(1)
(1)

Packaged ‘double ducts’ units (known commercially as `double ducts') defined as `Air conditioner completely positioned inside the conditioned space, with the condenser air intake and air discharge connected to the outside by means of two ducts', will be classified according to Table 1.2 with a correction factor of –0.4.

A3.00<EER
B3.00≥EER>2.80
C2.80≥EER>2.60
D2.60≥EER>2.40
E2.40≥EER>2.20
F2.20≥EER>2.00
G2.00≥EER
Table 1.3
Energy Efficiency classSingle-duct
A2.60<EER
B2.60≥EER>2.40
C2.40≥EER>2.20
D2.20≥EER>2.00
E2.00≥EER>1.80
F1.80≥EER>1.60
G1.60≥EER

Table 2—Water-cooled air conditioners

Table 2.1
Energy Efficiency classSplit and multi-split appliances
A3.60<EER
B3.60≥EER>3.30
C3.30≥EER>3.10
D3.10≥EER>2.80
E2.80≥EER>2.50
F2.50≥EER>2.20
G2.20≥EER
Table 2.2
Energy Efficiency classPackaged
A4.40<EER
B4.40≥EER>4.10
C4.10≥EER>3.80
D3.80≥EER>3.50
E3.50≥EER>3.20
F3.20≥EER>2.90
G2.90≥EER