PART 7SUPPLIES TO INSTALLATIONS AND TO OTHER NETWORKS

Information to be provided on request29.

A distributor shall provide, in respect of any existing or proposed consumer’s installation which is connected or is to be connected to their network, to any person who can show a reasonable cause for requiring the information, a written statement of—

(a)

the maximum prospective short circuit current at the supply terminals;

(b)

for low voltage connections, the maximum earth loop impedance of the earth fault path outside the installation;

(c)

the type and rating of the distributor’s protective device or devices nearest to the supply terminals;

(d)

the type of earthing system applicable to the connection; and

(e)

the information specified in regulation 28(1),

which apply, or will apply, to that installation.