  Demand disconnection starting mandatory level:    Frequency  ,49,48,7 – 48,8,48,8,48,85,Hz,
  Demand disconnection starting mandatory level:    Demand to be disconnected  ,5,5,5,6,% of the Total Load at national level,
  Demand disconnection final mandatory level:    Frequency  ,48,48,48,48,5,Hz,
  Demand disconnection final mandatory level:    Cumulative Demand to be disconnected  ,45,30,50,60,% of the Total Load at national level,
Implementation range,± 7,± 10,± 10,± 7,% of the Total Load at national level, for a given Frequency,
Minimum number of steps to reach the final mandatory level,6,2,4,6,Number of steps,
Maximum Demand disconnection for each step,10,15,10,12,% of the Total Load at national level, for a given step,