PART IIOPERATIONAL SECURITY
TITLE 2DATA EXCHANGE
CHAPTER 4Data exchange between TSOs, owners of interconnectors or other lines and power generating modules connected to the transmission system
Article 47Real-time data exchange
1.
Unless otherwise provided by the TSO, each significant grid user which is a power generating facility owner of type B, C or D power generating module shall provide the TSO, in real-time, at least the following data:
(a)
position of the circuit breakers at the connection point or another point of interaction agreed with the TSO;
(b)
active and reactive power at the connection point or another point of interaction agreed with the TSO; and
(c)
in the case of power generating facility with consumption other than auxiliary consumption net active and reactive power.
2.
Unless otherwise provided by the TSO, each HVDC system or AC interconnector owner shall provide, in real-time, at least the following data regarding the connection point of the HVDC system or AC interconnector to the TSOs:
(a)
position of the circuit breakers;
(b)
operational status; and
(c)
active and reactive power.