Commission Delegated Regulation (EU) 2016/364
of 1 July 2015
on the classification of the reaction to fire performance of construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council
(Text with EEA relevance)
THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Whereas:
Decision 2000/147/EC provides several classes of reaction to fire performance. In addition, it contains classes F, FFL, FL and Fca, which are defined as ‘no performance determined’.
In accordance with Article 2(7) of Regulation (EU) No 305/2011, a class means a range of levels, delimited by a minimum and a maximum value of performance. Classes defined as ‘no performance determined’ do not correspond to this definition and thus cannot be incorporated in a classification system under Regulation (EU) No 305/2011.
The use of ‘no performance determined’ in the context of drawing up the declaration of performance is provided in Article 6(3)(f) of Regulation (EU) No 305/2011.
In order to enable the manufacturers to declare lower reaction to fire performance than that covered by classes E, EFL, EL and Eca, it is necessary to change the classification criteria of classes F, FFL, FL and Fca accordingly.
It is therefore necessary to replace the classes F, FFL, FL and Fca provided in Decision 2000/147/EC with new classes for products not reaching at least the reaction to fire performance under the classes E, EFL, EL and Eca.
Decision 2000/147/EC has been amended several times and further amendments to that Decision are necessary. In the interests of clarity and rationality that decision should therefore be repealed and replaced,
HAS ADOPTED THIS REGULATION:
Article 1
When the intended use of a construction product is such that the product may contribute to the generation and spread of fire and smoke within the room or area of origin or beyond, the performance of the product in relation to its reaction to fire shall be classified in accordance with the classification system set out in the Annex.
Article 2
Decision 2000/147/EC is repealed.
References to the repealed Decision shall be construed as references to this Regulation.
Article 3
This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union.
This Regulation shall be binding in its entirety and directly applicable in all Member States.
Done at Brussels, 1 July 2015.
For the Commission
The President
Jean-Claude Juncker
ANNEXClasses of reaction to fire performance
1.1.For the purposes of Tables 1 to 4 the following symbols3 apply:
- (1) ‘ΔΤ’
temperature rise;
- (2) ‘Δm’
mass loss;
- (3) ‘tf’
duration of flaming;
- (4) ‘PCS’
gross calorific potential;
- (5) ‘LFS’
lateral flame spread;
- (6) ‘SMOGRA’
smoke growth rate.
1.2.For the purposes of Tables 1, 2 and 3 the following symbols3 apply:
- (1) ‘FIGRA’
fire growth rate;
- (2) ‘THR’
total heat release;
- (3) ‘TSP’
total smoke production;
- (4) ‘Fs’
flame spread.
1.3.For the purposes of Table 4 the following symbols and test parameters apply:
- (1) ‘HRRsm30, kW’
heat release rate averaged by a 30-s sliding average;
- (2) ‘SPRsm60, m2/s’
smoke production rate averaged by a 60-s sliding average;
- (3) ‘Peak HRR, kW’
maximum of HRRsm30 between test start and end of test, excluded contribution from ignition source;
- (4) ‘Peak SPR, m2/s’
maximum of SPRsm60 between test start and end of test;
- (5) ‘THR1200, MJ’
total heat release (HRRsm30) from test start until end of test, excluded contribution from ignition source;
- (6) ‘TSP1200, m2’
total smoke production (HRRsm60) from test start until end of test;
- (7) ‘FIGRA, W/s’
fire growth rate index defined as the highest value of the quotient between HRRsm30 excluding the contribution of ignition source and time. Threshold values HRRsm30 = 3 kW and THR = 0,4 MJ;
- (8) ‘FS’
flame spread (damaged length);
- (9) ‘H’
flame spread.
2.For the purposes of Tables 1 to 4 the following definitions apply:
- (1)
‘material’ means a single basic substance or uniformly dispersed mixture of substances;
- (2)
‘homogeneous product’ means a product consisting of a single material, having uniform density and composition throughout the product;
- (3)
‘non-homogeneous product’ means a product that does not satisfy the requirements of a homogeneous product and that is composed of one or more components, substantial and/or non-substantial;
- (4)
‘substantial component’ means a material that constitutes a significant part of a non-homogeneous product; a layer with a mass per unit area ≥ 1,0 kg/m2 or a thickness ≥ 1,0 mm is considered to be a substantial component;
- (5)
‘non-substantial component’ means a material that does not constitute a significant part of a non-homogeneous product; a layer with a mass per unit area < 1,0 kg/m2 and a thickness < 1,0 mm is considered to be a non-substantial component;
- (6)
‘internal non-substantial component’ means a non-substantial component that is covered on both sides by at least one substantial component;
- (7)
‘external non-substantial component’ means a non-substantial component that is not covered on one side by a substantial component.
Two or more non-substantial layers that are adjacent to each other, where there are no substantial components in between the layers, shall be considered as one non-substantial component and shall, therefore, be classified in accordance with the criteria for a layer that is a non-substantial component.
Class | Test method(s) | Classification criteria | Additional classification |
|---|---|---|---|
A1 | EN ISO 11824; and | ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (i.e. no sustained flaming) | |
EN ISO 1716 | PCS ≤ 2,0 MJkg– 1 4; and PCS ≤ 1,4 MJm– 2
7; and
PCS ≤ 2,0 MJkg– 1
8
| ||
A2 | EN ISO 11824; or | ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s | |
EN ISO 1716; and | PCS ≤ 3,0 MJkg– 1 4; and PCS ≤ 4,0 MJm– 2 5; and PCS ≤ 4,0 MJm– 2 7; and PCS ≤ 3,0 MJkg– 1 8 | ||
EN 13823 (SBI) | FIGRA ≤ 120 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ | Smoke production9; and
Flaming droplets/particles10
| |
B | EN 13823 (SBI); and | FIGRA ≤ 120 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ | Smoke production9; and Flaming droplets/particles10 |
EN ISO 11925-212: Exposure = 30 s | Fs ≤ 150 mm within 60 s | ||
C | EN 13823 (SBI); and | FIGRA ≤ 250 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 15 MJ | Smoke production9; and Flaming droplets/particles10 |
EN ISO 11925-212: Exposure = 30 s | Fs ≤ 150 mm within 60 s | ||
D | EN 13823 (SBI); and | FIGRA ≤ 750 Ws– 1 | Smoke production9; and Flaming droplets/particles10 |
EN ISO 11925-212: Exposure = 30 s | Fs ≤ 150 mm within 60 s | ||
E | EN ISO 11925-212: Exposure = 15 s | Fs ≤ 150 mm within 20 s | Flaming droplets/particles11 |
F | EN ISO 11925-212: Exposure = 15 s | Fs > 150 mm within 20 s |
Class | Test method(s) | Classification criteria | Additional classification |
|---|---|---|---|
A1FL | EN ISO 118213; and | ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (i.e. no sustained flaming) | |
EN ISO 1716 | PCS ≤ 2,0 MJkg– 1 13; and PCS ≤ 2,0 MJkg– 1
14; and
PCS ≤ 1,4 MJm– 2
15; and
PCS ≤ 2,0 MJkg– 1
16
| ||
A2FL | EN ISO 118213; or | ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s | |
EN ISO 1716; and | PCS ≤ 3,0 MJkg– 1 13; and PCS ≤ 4,0 MJm– 2 14; and PCS ≤ 4,0 MJm– 2 15; and PCS ≤ 3,0 MJkg– 1 16 | ||
EN ISO 9239-117 | Critical flux18 ≥ 8,0 kWm– 2 | Smoke production19 | |
BFL | EN ISO 9239-117 and | Critical flux18 ≥ 8,0 kWm– 2 | Smoke production19 |
EN ISO 11925-220: Exposure = 15 s | Fs ≤ 150 mm within 20 s | ||
CFL | EN ISO 9239-117 and | Critical flux18 ≥ 4,5 kWm– 2 | Smoke production19 |
EN ISO 11925-220: Exposure = 15 s | Fs ≤ 150 mm within 20 s | ||
DFL | EN ISO 9239-117 and | Critical flux18 ≥ 3,0 kWm– 2 | Smoke production19 |
EN ISO 11925-220: Exposure = 15 s | Fs ≤ 150 mm within 20 s | ||
EFL | EN ISO 11925-220: Exposure = 15 s | Fs ≤ 150 mm within 20 s | |
FFL | EN ISO 11925-220: Exposure = 15 s | Fs > 150 mm within 20 s |
Class | Test method(s) | Classification criteria | Additional classification |
|---|---|---|---|
A1L | EN ISO 118221; and | ΔT ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (i.e. no sustained flaming) | |
EN ISO 1716 | PCS ≤ 2,0 MJkg– 1 21; and PCS ≤ 2,0 MJkg– 1
22; and
PCS ≤ 1,4 MJm– 2
23; and
PCS ≤ 2,0 MJkg– 1
24
| ||
A2L | EN ISO 118221; or | ΔT ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s | |
EN ISO 1716; and | PCS ≤ 3,0 MJkg– 1 21; and PCS ≤ 4,0 MJm– 2 22; and PCS ≤ 4,0 MJm– 2 23; and PCS ≤ 3,0 MJkg– 1 24 | ||
EN 13823 (SBI) | FIGRA ≤ 270 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ | Smoke production25; and
Flaming droplets/particles26
| |
BL | EN 13823 (SBI); and | FIGRA ≤ 270 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ | Smoke production25; and Flaming droplets/particles26 |
EN ISO 11925-228: Exposure = 30 s | Fs ≤ 150 mm within 60 s | ||
CL | EN 13823 (SBI); and | FIGRA ≤ 460 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 15 MJ | Smoke production25; and Flaming droplets/particles26 |
EN ISO 11925-228: Exposure = 30 s | Fs ≤ 150 mm within 60 s | ||
DL | EN 13823 (SBI); and | FIGRA ≤ 2 100 Ws– 1 THR600s ≤ 100 MJ | Smoke production25; and Flaming droplets/particles26 |
EN ISO 11925-228: Exposure = 30 s | Fs ≤ 150 mm within 60 s | ||
EL | EN ISO 11925-228: Exposure = 15 s | Fs ≤ 150 mm within 20 s | Flaming droplets/particles27 |
FL | EN ISO 11925-228: Exposure = 15 s | Fs > 150mm within 20 s |
Class | Test method(s) | Classification criteria | Additional classification |
|---|---|---|---|
Aca | EN ISO 1716 | PCS ≤ 2,0 MJ/kg29 | |
B1ca | EN 50399 (30 kW flame source) and | FS ≤ 1,75 m and THR1200s ≤ 10 MJ and Peak HRR ≤ 20 kW and FIGRA ≤ 120 Ws– 1 | |
EN 60332-1-2 | H ≤ 425 mm | ||
B2ca | EN 50399 (20,5 kW flame source) and | FS ≤ 1,5 m; and THR1200s ≤ 15 MJ; and Peak HRR ≤ 30 kW; and FIGRA ≤ 150 Ws– 1 | |
EN 60332-1-2 | H ≤ 425 mm | ||
Cca | EN 50399 (20,5 kW flame source) and | FS ≤ 2,0 m; and THR1200s ≤ 30 MJ; and Peak HRR ≤ 60 kW; and FIGRA ≤ 300 Ws– 1 | Smoke production3034 and Flaming droplets/particles31 and Acidity (pH and conductivity)32 |
EN 60332-1-2 | H ≤ 425 mm | ||
Dca | EN 50399 (20,5 kW flame source) and | THR1200s ≤ 70 MJ; and Peak HRR ≤ 400 kW; and FIGRA ≤ 1 300 Ws– 1 | Smoke production3034 and Flaming droplets/particles31 and Acidity (pH and conductivity)32 |
EN 60332-1-2 | H ≤ 425 mm | ||
Eca | EN 60332-1-2 | H ≤ 425 mm | |
Fca | EN 60332-1-2 | H > 425 mm |