TITLE IIGENERAL REQUIREMENTS FOR HVDC CONNECTIONS
CHAPTER 1 Requirements for active power control and frequency support
Article 11Frequency ranges
1.
An HVDC system shall be capable of staying connected to the network and remaining operable within the frequency ranges and time periods specified in Table 1, Annex I for the short circuit power range as specified in Article 32(2).
2.
The relevant TSO and HVDC system owner may agree on wider frequency ranges or longer minimum times for operation if needed to preserve or to restore system security. If wider frequency ranges or longer minimum times for operation are economically and technically feasible, the HVDC system owner shall not unreasonably withhold consent.
3.
Without prejudice to paragraph 1, an HVDC system shall be capable of automatic disconnection at frequencies specified by the relevant TSO.
4.
The relevant TSO may specify a maximum admissible active power output reduction from its operating point if the system frequency falls below 49 Hz.