47,0 Hz-47,5 Hz,60 seconds,
47,5 Hz-48,5 Hz,To be specified by each relevant TSO, but longer than established times for generation and demand according to Regulation (EU) 2016/631 and Regulation (EU) 2016/1388 respectively, and longer than for DC-connected PPMs according to Article 39,
48,5 Hz-49,0 Hz,To be specified by each relevant TSO, but longer than established times for generation and demand according to Regulation (EU) 2016/631 and Regulation (EU) 2016/1388 respectively, and longer than for DC-connected PPMs according to Article 39,
49,0 Hz-51,0 Hz,Unlimited,
51,0 Hz-51,5 Hz,To be specified by each relevant TSO, but longer than established times for generation and demand according to Regulation (EU) 2016/631 and Regulation (EU) 2016/1388 respectively, and longer than for DC-connected PPMs according to Article 39,
51,5 Hz-52,0 Hz,To be specified by each relevant TSO, but longer than for DC-connected PPMs according to Article 39,

Frequency response deadband,0-±500 mHz,
Droop s  1 (upward regulation),Minimum 0,1 %,
Droop s  2 (downward regulation),Minimum 0,1 %,
Frequency response insensitivity,Maximum 30 mHz,

Maximum admissible initial delay t  1 ,0,5 seconds,
Maximum admissible time for full activation t  2 , unless longer activation times are specified by the relevant TSO,30 seconds,

Continental Europe,0,85 pu-1,118 pu,Unlimited,
1,118 pu-1,15 pu,To be established by each relevant system operator, in coordination with the relevant TSO but not less than 20 minutes,
Nordic,0,90 pu-1,05 pu,Unlimited,
1,05 pu-1,10 pu,60 minutes,
Great Britain,0,90 pu-1,10 pu,Unlimited,
Ireland and Northern Ireland,0,90 pu-1,118 pu,Unlimited,
Baltic,0,85 pu-1,118 pu,Unlimited,
1,118 pu-1,15 pu,20 minutes,

Continental Europe,0,85 pu-1,05 pu,Unlimited,
1,05 pu-1,0875 pu,To be specified by each TSO, but not less than 60 minutes,
1,0875 pu-1,10 pu,60 minutes,
Nordic,0,90 pu-1,05 pu,Unlimited,
1,05 pu-1,10 pu,To be specified by each TSO, but not more than 60 minutes,
Great Britain,0,90 pu-1,05 pu,Unlimited,
1,05 pu-1,10 pu,15 minutes,
Ireland and Northern Ireland,0,90 pu-1,05 pu,Unlimited,
Baltic,0,88 pu-1,097 pu,Unlimited,
1,097 pu-1,15 pu,20 minutes,

Continental Europe,0,95,0,225,
Nordic,0,95,0,15,
Great Britain,0,95,0,225,
Ireland and Northern Ireland,1,08,0,218,
Baltic States,1,0,0,220,

U ret ,0,00-0,30,t clear ,0,14-0,25,
U rec1 ,0,25-0,85,t rec1 ,1,5-2,5,
U rec2 ,0,85-0,90,t rec2 ,T rec1 -10,0,

47,0 Hz-47,5 Hz,20 seconds,
47,5 Hz-49,0 Hz,90 minutes,
49,0 Hz-51,0 Hz,Unlimited,
51,0 Hz-51,5 Hz,90 minutes,
51,5 Hz-52,0 Hz,15 minutes,

0,85 pu-0,90 pu,60 minutes,
0,90 pu-1,10 pu,Unlimited,
1,10 pu-1,118 pu,Unlimited, unless specified otherwise by the relevant system operator, in coordination with the relevant TSO.,
1,118 pu-1,15 pu,To be specified by the relevant system operator, in coordination with the relevant TSO.,

0,85 pu-0,90 pu,60 minutes,
0,90 pu-1,05 pu,Unlimited,
1,05 pu-1,15 pu,To be specified by the relevant system operator, in coordination with the relevant TSO. Various sub-ranges of voltage withstand capability can be specified.,

0-0,95,0,1-0,225,

0,85 pu-0,90 pu,60 minutes,
0,90 pu-1,10 pu,Unlimited,
1,10 pu-1,12 pu,Unlimited, unless specified otherwise by the relevant system operator, in coordination with the relevant TSO.,
1,12 pu-1,15 pu,To be specified by the relevant system operator, in coordination with the relevant TSO.,

0,85 pu-0,90 pu,60 minutes,
0,90 pu-1,05 pu,Unlimited,
1,05 pu-1,15 pu,To be specified by the relevant system operator, in coordination with the relevant TSO. Various sub-ranges of voltage withstand capability may be specified.,

0,95,0,225,