The installer shall take all measures necessary to ensure that the lift being installed complies with the applicable essential health and safety requirements set out in Annex I and with one of the following:
an approved type described in an EU-type examination certificate;
a lift designed and manufactured in accordance with a quality system pursuant to Annex XI and the EU design examination certificate if the design is not wholly in accordance with the harmonised standards.
A notified body chosen by the installer shall carry out the final inspection of the lift about to be placed on the market in order to check the conformity of the lift with the applicable essential health and safety requirements set out in Annex I.
the plan of the complete lift;
the plans and diagrams necessary for final inspection, in particular control circuit diagrams;
a copy of the instructions referred to in Annex I, point 6.2;
a written declaration that the same application has not been lodged with any other notified body.
The notified body may not require detailed plans or precise information not necessary for verifying the conformity of the lift.
The appropriate examinations and tests set out in the relevant harmonised standard(s) or equivalent tests shall be carried out in order to check the conformity of the lift with the applicable essential health and safety requirements set out in Annex I.
examination of the documents referred to in point 3.1 to check that the lift conforms with the approved type described in the EU-type examination certificate pursuant to Annex IV, Part B;
examination of the documents referred to in point 3.1 to check that the lift conforms with the lift designed and manufactured in accordance with an approved quality system pursuant to Annex XI and if the design is not wholly in accordance with the harmonised standards, with the EU design examination certificate.
operation of the lift both empty and at maximum load to ensure correct installation and operation of the safety devices (end stops, locking devices, etc.);
operation of the lift at both maximum load and empty to ensure the correct functioning of the safety devices in the event of loss of power;
static test with a load equal to 1,25 times the rated load.
The rated load shall be that referred to in Annex I, point 5.
After these tests, the notified body shall check that no distortion or deterioration which could impair the use of the lift has occurred.
The notified body shall fill in the corresponding pages in the logbook referred to in Annex I, point 6.2.
If the notified body refuses to issue the final inspection certificate, it shall state the detailed reasons for refusal and indicate the necessary corrective measures to be taken. Where the installer again applies for final inspection, he shall apply to the same notified body.
The installer’s obligations set out in points 3.1 and 5 may be fulfilled by his authorised representative, on his behalf and under his responsibility, provided that they are specified in the mandate.