ANNEX IREQUIREMENTS FOR URBAN WASTE WATER

A.Collecting systems6

Collecting systems shall take into account waste water treatment requirements.

The design, construction and maintenance of collecting systems shall be undertaken in accordance with the best technical knowledge not entailing excessive costs, notably regarding:

  • volume and characteristics of urban waste water,

  • prevention of leaks,

  • limitation of pollution of receiving waters due to storm water overflows.

B.Discharge from urban waste water treatment plants to receiving waters6

1.

Waste water treatment plants shall be designed or modified so that representative samples of the incoming waste water and of treated effluent can be obtained before discharge to receiving waters.

2.

Discharges from urban waste water treatment plants subject to treatment in accordance with Articles 4 and 5 shall meet the requirements shown in Table 1.

3.

Discharges from urban waste water treatment plants to those sensitive areas which are subject to eutrophication as identified in Annex II.A (a) shall in addition meet the requirements shown in Table 2 of this Annex.

4.

More stringent requirements than those shown in Table 1 and/or Table 2 shall be applied where required to ensure that the receiving waters satisfy any other relevant Directives.

5.

The points of discharge of urban waste water shall be chosen, as far as possible, so as to minimize the effects on receiving waters.

C.Industrial waste water

Industrial waste water entering collecting systems and urban waste water treatment plants shall be subject to such pre-treatment as is required in order to:

  • protect the health of staff working in collecting systems and treatment plants,

  • ensure that collecting systems, waste water treatment plants and associated equipment are not damaged,

  • ensure that the operation of the waste water treatment plant and the treatment of sludge are not impeded,

  • ensure that discharges from the treatment plants do not adversely affect the environment, or prevent receiving water from complying with other Community Directives,

  • ensure that sludge can be disposed of safety in an environmentally acceptable manner.

D.Reference methods for monitoring and evaluation of results

1.

Member States shall ensure that a monitoring method is applied which corresponds at least with the level of requirements described below.

Alternative methods to those mentioned in paragraphs 2, 3 and 4 may be used provided that it can be demonstrated that equivalent results are obtained.

Member States shall provide the Commission with all relevant information concerning the applied method. If the Commission considers that the conditions set out in paragraphs 2, 3 and 4 are not met, it will submit an appropriate proposal to the Council.

2.

Flow-proportional or time-based 24-hour samples shall be collected at the same well-defined point in the outlet and if necessary in the inlet of the treatment plant in order to monitor compliance with the requirements for discharged waste water laid down in this Directive.

Good international laboratory practices aiming at minimizing the degradation of samples between collection and analysis shall be applied.

3.

The minimum annual number of samples shall be etermined according to the size of the treatment plant and be collected at regular intervals during the year:

— 2 000 to 9 999 p.e.:

12 samples during the first year.

four samples in subsequent years, if it can be shown that the water during the first year complies with the provisions of the Directive; if one sample of the four fails, 12 samples must be taken in the year that follows.

— 10 000 to 49 999 p. e.:

12 samples.

— 50 000 p.e. or over:

24 samples.

4.

The treated waste water shall be assumed to conform to the relevant parameters if, for each relevant parameter considered individually, samples of the water show that it complies with the relevant parametric value in the following way:

  1. (a)

    for the parameters specified in Table 1 and Article 2 (7), a maximum number of samples which are allowed to fail the requirements, expressed in concentrations and/or percentage reductions in Table 1 and Article 2 (7), is specified in Table 3;

  2. (b)

    for the parameters of Table 1 expressed in concentrations, the failing samples taken under normal operating conditions must not deviate from the parametric values by more than 100 %. For the parametric values in concentration relating to total suspended solids deviations of up to 150 % may be accepted;

  3. (c)

    for those parameters specified in Table 2 the annual mean of the samples for each parameter shall conform to the relevant parametric values.

5.

Extreme values for the water quality in question shall not be taken into consideration when they are the result of unusual situations such as those due to heavy rain.

Table 1:Requirements for discharges from urban waste water treatment plants subject to Articles 4 and 5 of the Directive. The values for concentration or for the percentage of reduction shall apply.

Parameters

Concentration

Minimum percentage of reduction7

Reference method of measurement

Biochemical oxygen demand (BOD5 at 20 °C) without nitrification8

25 mg/l O2

70-90

40 under Article 4 (2)

Homogenized, unfiltered, undecanted sample. Determination of dissolved oxygen before and after five-day incubation at 20 °C ± 1 °C, in complete darkness. Addition of a nitrification inhibitor

Chemical oxygen demand (COD)

125 mg/l O2

75

Homogenized, unfiltered, undecanted sample Potassium dichromate

Total suspended solids

35 mg/l9

35 under Article 4 (2) (more than 10 000 p.e.)

60 under Article 4 (2) (2 000-10 000 p.e.)

909

90 under Article 4 (2) (more than 10 000 p.e.)

70 under Article 4 (2) (2 000-10 000 p.e.)

  • Filtering of a representative sample through a 0,45 μm filter membrane. Drying at 105 °C and weighing

  • Centrifuging of a representative sample (for at least five mins with mean acceleration of 2 800 to 3 200 g), drying at 105 °C and weighing

Reduction in relation to the load of the influent.

The parameter can be replaced by another parameter: total organic carbon (TOC) or total oxygen demand (TOD) if a relationship can be established between BOD5 and the substitute parameter.

This requirement is optional.

Analyses concerning discharges from lagooning shall be carried out on filtered samples; however, the concentration of total suspended solids in unfiltered water samples shall not exceed 150 mg/l.

F1Table 2:

X1Requirements for discharges from urban waste water treatment plants to sensitive areas which are subject to eutrophication as identified in Annex II.A(a). One or both parameters may be applied depending on the local situation. The values for concentration or for the percentage of reduction shall apply.

Parameters

Concentration

Minimum percentage of reduction11

Reference method of measurement

Total phosphorus

X22 mg/l (10 000100 000 p.e.)

80

Molecular absorption spectrophotometry

1 mg/l (more than 100 000 p.e.)

Total nitrogen12

15 mg/l (10 000-100 000 p.e.)13

70-80

Molecular absorption spectrophotometry

10 mg/l (more than 100 000 p.e.)13

Reduction in relation to the load of the influent.

Total nitrogen means the sum of total Kjeldahl nitrogen (organic and ammoniacal nitrogen) nitrate-nitrogen and nitrite-nitrogen.

These values for concentration are annual means as referred to in Annex I, paragraph D.4(c). However, the requirements for nitrogen may be checked using daily averages when it is proved, in accordance with Annex I, paragraph D.1, that the same level of protection is obtained. In this case, the daily average must not exceed 20 mg/l of total nitrogen for all the samples when the temperature from the effluent in the biological reactor is superior or equal to 12 °C. The conditions concerning temperature could be replaced by a limitation on the time of operation to take account of regional climatic conditions.

Table 3

Series of samples taken in any year

Maximum permitted number of samples which fail to conform

4-7

1

8-16

2

17-28

3

29-40

4

41-53

5

54-67

6

68-81

7

82-95

8

96-110

9

111-125

10

126-140

11

141-155

12

156-171

13

172-187

14

188-203

15

204-219

16

220-235

17

236-251

18

252-268

19

269-284

20

285-300

21

301-317

22

318-334

23

335-350

24

351-365

25