Commission Decision
of 17 January 2003
establishing the classes of reaction-to-fire performance for certain construction products
(notified under document number C(2002) 4807)
(Text with EEA relevance)
(2003/43/EC)
THE COMMISSION OF THE EUROPEAN COMMUNITIES,
Having regard to the Treaty establishing the European Community,
Whereas:
‘Communication of the Commission with regard to the interpretative documents of Council Directive 89/106/EEC3
With respect to the essential requirement of safety in the event of fire, interpretative document No 2 lists a number of interrelated measures which together define the fire safety strategy to be variously developed in the Member States.
Interpretative document No 2 identifies one of those measures as the limitation of the generation and spread of fire and smoke within a given area by limiting the potential of construction products to contribute to the full development of a fire.
The level of that limitation may be expressed only in terms of the different levels of reaction-to-fire performance of the products in their end-use application.
In the case of certain wood-based panels, it is necessary to use the classification established in Decision 2000/147/EC.
The reaction-to-fire performance of many construction products and/or materials, within the classification provided for in Decision 2000/147/EC, is well established and sufficiently well known to fire regulators in Member States that they do not require testing for this particular performance characteristic.
The measures provided for in this Decision are in accordance with the opinion of the Standing Committee on Construction,
HAS ADOPTED THIS DECISION:
Article 1
The construction products and/or materials which satisfy all the requirements of the performance characteristic ‘reaction-to-fire’ without need for further testing are set out in the Annex.
Article 2
The specific classes to be applied to different construction products and/or materials, within the reaction-to-fire classification adopted in Decision 2000/147/EC, are set out in the Annex to this Decision.
Article 3
Products shall be considered in relation to their end-use application, where relevant.
Article 4
This Decision is addressed to the Member States.
ANNEX
The tables set out in this annex list construction products and/or materials which satisfy all the requirements for the performance characteristic reaction to fire without need for testing.
Product | EN product standard | End use condition10 | Minimum density(kg/m 3 ) | Minimum thickness(mm) | Class11(excluding floorings) | Class12(floorings) |
|---|---|---|---|---|---|---|
Cement-bonded particleboard5 | EN 634-2 | without an air gap behind the panel | 1 000 | 10 | B-s1, d0 | B fl -s1 |
Fibreboard, hard5 | EN 622-2 | without an air gap behind the wood-based panel | 900 | 6 | D-s2, d0 | D fl -s1 |
Fibreboard, hard7 | EN 622-2 | with a closed air gap not more than 22 mm behind the wood-based panel | 900 | 6 | D-s2, d2 | — |
EN 312 | without an air gap behind the wood-based panel | 600 | 9 | D-s2, d0 | D fl -s1 | |
EN 622-2 EN 622-3 | ||||||
EN 622-5 | ||||||
EN 300 | ||||||
EN 636 | -“- | 400 | 9 | D-s2, d0 | D fl -s1 | |
EN 13353 | 12 | |||||
EN 15197 | -“- | 450 | 15 | D-s2, d0 | D fl -s1 | |
EN 312 | with a closed or an open air gap not more than 22 mm behind the wood-based panel | 600 | 9 | D-s2, d2 | — | |
EN 622-2 EN 622-3 | ||||||
EN 622-5 | ||||||
EN 300 | ||||||
EN 636 | -“- | 400 | 9 | D-s2, d2 | — | |
EN 13353 | 12 | |||||
EN 312 | with a closed air gap behind the wood-based panel | 600 | 15 | D-s2, d0 | D fl -s1 | |
EN 622-3 | ||||||
EN 622-5 | ||||||
EN 300 | ||||||
EN 636 | -“- | 400 | 15 | D-s2, d1 | D fl -s1 | |
EN 13353 | D-s2, d0 | |||||
EN 15197 | -“- | 450 | 15 | D-s2, d0 | D fl -s1 | |
EN 312 | with an open air gap behind the wood-based panel | 600 | 18 | D-s2, d0 | D fl -s1 | |
EN 622-3 | ||||||
EN 622-5 | ||||||
EN 300 | ||||||
EN 636 | -“- | 400 | 18 | D-s2, d0 | D fl -s1 | |
EN 13353 | ||||||
EN 15197 | -“- | 450 | 18 | D-s2, d0 | D fl -s1 | |
Particleboard9 | EN 312 | any | 600 | 3 | E | E fl |
OSB9 | EN 300 | |||||
MDF9 | EN 622-5 | -“- | 400 | 3 | E | E fl |
250 | 9 | E | E fl | |||
Plywood9 | EN 636 | -“- | 400 | 3 | E | E fl |
Fibreboard, hard9 | EN 622-2 | -“- | 900 | 3 | E | E fl |
Fibreboard, medium9 | EN 622-3 | -“- | 400 | 9 | E | E fl |
Fibreboard, soft | EN 622-4 | -“- | 250 | 9 | E | E fl |
Gypsum plasterboard | Nominal board thickness (mm) | Gypsum core |
Paper grammage
13
(g/m
2
)
| Substrate |
Class
14
(excluding floorings)
| |
|---|---|---|---|---|---|---|
Density (kg/m 3 ) | Reaction to fire class | |||||
Conforming to EN 520 (except perforated boards) | ≥ 6,5 < 9,5 | ≥ 800 | A1 | ≤ 220 | Any wood-based product with density ≥ 400 kg/m 3 or any product of at least class A2-s1, d0 | A2-s1, d0 |
> 220 ≤ 320 | B-s1, d0 | |||||
≥ 9,5 | ≥ 600 | ≤ 220 | Any wood-based product with density ≥ 400 kg/m 3 or any product of at least class A2-s1, d0 or any insulating product of at least class E-d2 mounted according to method 1 | A2-s1, d0 | ||
> 220 ≤ 320 | B-s1, d0 | |||||
Note:
Mounting and fixing
The gypsum plasterboards (hereinafter — ‘ gypsum boards ’ ) shall be mounted and fixed using one of the three following methods:
Method 1 — Mechanically fixed to a supporting substructure
The gypsum boards, or (in the case of multi-layer systems) at least the outermost layer of boards, shall be mechanically fixed to a metal substructure (made from components detailed in EN 14195) or to a timber substructure (in accordance with EN 336 and EN 1995-1-1).
When the substructure provides supporting members in one direction only, the maximum span between the supporting members shall not exceed a dimension equal to 50 times the thickness of the gypsum boards.
When the substructure includes supporting members in two directions the maximum span in either direction shall not exceed a dimension equal to 100 times the thickness of the gypsum boards.
The mechanical fixings shall be screws, staples or nails, which shall be fixed through the thickness of the gypsum boards into the substructure at centres not exceeding 300 mm measured along the length of each supporting member.
Behind the gypsum boards may be an air space, or an insulating product. The substrate may be:
- (a)
any wood-based product with density ≥ 400 kg/m 3 or any product of at least class A2-s1, d0 in case of gypsum boards of ≥ 6,5 mm and < 9,5 mm nominal thickness and ≥ 800 kg/m 3 core density, or
- (b)
any wood-based product with density ≥ 400 kg/m 3 or any product of at least class A2-s1, d0 in case of gypsum boards of ≥ 9,5 mm nominal thickness and ≥ 600 kg/m 3 core density, or
- (c)
any insulating material of at least class E-d2 in case of gypsum boards of ≥ 9,5 mm nominal thickness and ≥ 600 kg/m 3 core density.
Each joint between adjoining gypsum boards shall have a gap width ≤ 4 mm. This provision applies for any joint regardless of that the joint is or is not supported directly by a substructure supporting member and regardless of that the joint is or is not filled with a jointing material.
In cases (a) and (b) each joint between adjoining gypsum boards, which is not supported directly by a substructure supporting member and which has a gap width > 1 mm, shall be fully filled with a jointing material as specified in EN 13963 (the other joints may remain unfilled).
In case (c) all joints between adjoining gypsum boards shall be fully filled with a jointing material as specified in EN 13963.
- (a)
Method 2 — Mechanically fixed to a solid wood-based substrate
The gypsum boards shall be mechanically fixed to a solid wood-based substrate with density ≥ 400 kg/m 3 .
There shall be no cavity between the gypsum boards and the substrate.
The mechanical fixings shall be screws, staples or nails. The distance between the mechanical fixings shall correspond to the rules given above for method 1.
Each joint between adjoining gypsum boards shall have a gap width ≤ 4 mm and may remain unfilled.
Method 3 — Mechanically fixed or bonded to a solid substrate (dry lining system)
The gypsum boards shall be fixed directly to a solid substrate with a reaction to fire classification of at least class A2-s1, d0.
The gypsum boards may be fixed using screws or nails fixed through the thickness of the gypsum boards into the solid substrate or may be bonded to the substrate using ‘ dabs ’ of a gypsum based adhesive as specified in EN 14496.
In either case the screw or nail fixings or the adhesive ‘ dabs ’ shall be positioned at maximum 600 mm vertical and horizontal centres.
All joints between adjoining gypsum boards may remain unfilled.
High pressure decorative laminate panels16 | Product detail | Minimum density(kg/m 3 ) | Minimum overall thickness(mm) | Class17(excluding floorings) |
|---|---|---|---|---|
Interior grade non-FR Compact HPL panels18 | Compact HPL meeting EN 438-4 type CGS | 1 350 | 6 | D-s2, d0 |
Interior grade non-FR HPL composite panels with wood-based substrates18 | Composite panels comprising non-FR grade HPL meeting the requirements of EN 438-3, adhesively bonded to both sides of non-FR grade wood-based core of minimum thickness 12 mm complying with EN 13986, using PVAc or thermosetting adhesive at an application rate of 60 to 120 g/m 2 | Wood-based core minimum density 600 HPL minimum density 1 350 | 12 mm wood-based core with HPL ≥ 0,5 mm bonded to both sides | D-s2, d0 |
Product detail | Minimum mean density21(kg/m
3
) | Minimum overall thickness(mm) | Class20(excluding floorings) | |
|---|---|---|---|---|
Structural timber | Visual and machine graded structural timber with rectangular cross-sections shaped by sawing, planing or other methods or with round cross-sections | 350 | 22 | D-s2, d0 |