Amendments to the Environmental Protection (Disposal of Polychlorinated Biphenyls and other Dangerous Substances) (England and Wales) Regulations 20002

1

The Environmental Protection (Disposal of Polychlorinated Biphenyls and other Dangerous Substances) (England and Wales) Regulations 20003 are amended as follows.

2

In regulation 2(1), in the definition of “PCBs”, for “4(3) and (4), 5(3), 6(2) and 9(3)” substitute “4(3A), (3C) and (4), 5(3) and 9(3)”.

3

In regulation 4—

a

in paragraph (1), for “(2), (3)” substitute “(2) to (3D)”;

b

for paragraph (3), substitute—

3A

Paragraph (3B) applies to a transformer in respect of which it is reasonable to assume that the fluids contain—

a

0.005% by weight, or less, of PCBs; or

b

a total volume of 0.05dm3, or less, of PCBs.

3B

A transformer to which this paragraph applies—

a

may be held until the end of its useful life; and

b

must then be decontaminated in accordance with paragraph (4)(b) to (d), or disposed of, as soon as possible.

3C

Paragraph (3D) applies to a transformer in respect of which it is reasonable to assume that the fluids contain—

a

more than 0.005% but no more than 0.05% by weight of PCBs; and

b

a total volume of more than 0.05dm3 of PCBs.

3D

A transformer to which this paragraph applies—

a

may be held until the end of 31st December 2025; and

b

must then be decontaminated in accordance with paragraph (4)(b) to (d), or disposed of, as soon as possible.

c

in paragraph (4)(a), for “less than 0.05% by weight and, if possible, to no more than 0.005% by weight” substitute “0.005% by weight, or less, or a total volume of 0.05dm3, or less”;

d

in paragraph (9)—

i

in paragraph (a), for “(2), (3)” substitute “(2) to (3D)”;

ii

in paragraphs (b) and (c), for “not contaminated”, in both places it occurs, substitute “relevant”;

e

after paragraph (9) insert—

10

In paragraph (9), “relevant equipment” means any equipment (including any capacitor or receptacle containing residual stocks) which—

a

contains PCBs; or

b

having contained PCBs, has not been decontaminated,

other than one which contains a total volume of PCBs exceeding 0.05dm3.

11

For the purposes of paragraph (10)—

a

the PCB volume of a power capacitor shall be measured by reference to all of the separate elements of a combined set; and

b

any thing of a type which may contain PCBs shall be treated as containing PCBs unless it is reasonable to assume the contrary.

4

For regulation 5(3) substitute—

3

Equipment in respect of which it is reasonable to assume that the fluids contain—

a

0.005% by weight, or less, of PCBs; or

b

a total volume of 0.05dm3, or less, of PCBs,

may be labelled as “PCBs contaminated <0.005% or <0.05dm3.

5

Omit regulation 6(2)(b).

6

In regulation 10, in paragraph (1), for “(2), (3)” substitute “(2) to (3D)”.

7

For regulation 13(2)(c)(i), substitute—

ia

in a case to which paragraph (3A) of regulation 4 applies, as soon as possible after the end of its useful life;

ib

in a case to which paragraph (3C) of regulation 4 applies, as soon as possible after 31st December 2025;

8

In regulation 13A(1), in the table, for the entry relating to regulation 13(2)(c)(i) substitute—

regulation 13(2)(c)(ia)

Yes

Yes

No

Yes

regulation 13(2)(c)(ib)

Yes

Yes

No

Yes

9

In regulation 13B(1), in the table, for the entry relating to regulation 13(2)(c)(i) substitute—

regulation 13(2)(c)(ia)

Yes

Yes

No

Yes

regulation 13(2)(c)(ib)

Yes

Yes

No

Yes