- Latest available (Revised)
- Original (As made)
This is the original version (as it was originally made). UK Statutory Instruments are not carried in their revised form on this site.
2. The declared net capacity of a generating station which is driven by water, wind or solar power shall be ascertained by the application of the formula
A × B
where—
A is the highest generation of electricity (at the main alternator terminals or, in the case of direct current generation, at the output terminals of the direct current to alternating current converter) which, on the assumption that the source of power is available uninterruptedly, can be maintained indefinitely without causing damage to the plant less so much of that electricity as is consumed by the plant; and
B has the value set out in the table as applicable to the particular description of station.
| (1) | (2) |
|---|---|
| Description of station | Value of B |
1. Station driven by tidal or wave power | 0.33 |
2. Station driven by any form of water power other than tidal or wave power | 1 |
3. Station driven by wind power | 0.43 |
4. Station driven by solar power | 0.17 |
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made):The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.