xmlns:atom="http://www.w3.org/2005/Atom"

Means for fighting fire

5.—(1) Subject to the provisions of this regulation, station premises shall be provided with such means for fighting fire as are appropriate and adequate in relation to the risk to persons in case of fire in the premises.

(2) The location of each fire hydrant in station premises shall be indicated by a distinctive and conspicuous notice in a position above or adjacent to the fire hydrant.

(3) The outlet connection of every fire hydrant in station premises shall be of such a type as is compatible with the type of attachment on hoses used by the fire brigade for the purpose of drawing water from fire hydrants.

(4) Every escalator and travolator in station premises shall be provided with a means for fighting fire comprising a water sprinkler system which is activated automatically on the operation of the means for detecting fire with which the escalator or travolator is provided under regulation 6(1) below.

(5) The following parts of station premises shall be provided with a means for fighting fire comprising a system which is activated automatically in such a part of the premises in the event of any outbreak of fire in that part of the premises, that is to say–

(a)a machine room, other than a machine room in which machinery for operating an escalator, travolator or lift is installed;

(b)any storage area, including an area set aside for storing refuse pending its disposal;

(c)any part of the premises used as a shop.

(6) All means for fighting fire in station premises shall be maintained in efficient working order and all portable equipment for fighting fire in the premises shall be so placed as to be readily available for use.

(7) When any person employed to work in station premises reasonably suspects that there is an outbreak of fire in the premises, immediate steps shall be taken to activate the system for giving warning in case of fire referred to in regulation 6(4) below and to call for the assistance of the fire brigade.

(8) A plan of the station premises suitable for use by members of the fire brigade when attending the premises for fire fighting purposes shall be kept in, or affixed to, a part of the premises where it is accessible to members of the fire brigade in such an event.