Regulation 12

SCHEDULE 4Sampling and Analysis

This schedule has no associated Explanatory Memorandum

PART 1General

Samples: general

1.  The Department must ensure that each sample taken in accordance with a monitoring programme is—

(a)representative of the water at the sampling point at the time of sampling;

(b)not contaminated in the course of being taken;

(c)for the chemical parameters copper, lead and nickel taken without prior flushing and is a random daytime sample of one litre volume;

(d)for chemical parameters in the distribution network be undertaken in accordance with ISO 5667-5, other than where the sample is taken from a consumer’s tap;

(e)for microbiological parameters taken and handled according to EN ISO 19458, sampling purpose A and B;

(f)kept at such temperature and in such conditions as will secure that there is no material alteration of a concentration, value or state of any parameter/measurement/observation for which the sample is to be analysed; and

(g)analysed as soon as may be possible after it has been taken—

(i)by a person who is competent to perform that task; and

(ii)with the use of such equipment as is suitable for the purpose.

Analysing samples

2.—(1) The Department must ensure each sample is analysed in accordance with this paragraph and that analysis methods used are validated and documented in accordance with EN ISO/IEC 17025 or other equivalent standards accepted at an international level.

(2) For each parameter specified in the first column of Table A in Part 2 of this Schedule “Table A” the method of analysis is specified in the second column of that table.

(3) For each parameter specified in the first column of Table B in Part 2 of this Schedule “Table B” the method of analysis must be capable of measuring concentrations equal to the parametric value with a limit of quantification of 30% or less of the relevant parametric value set in Schedule 1 and an uncertainty of measurement as specified in Table B.

(4) The Department must not use the uncertainty of measurement in Table B as an additional tolerance to the parametric values set in Schedule 1.

(5) For hydrogen ion, a method of analysis which is capable at the time of use of measuring a value with a trueness of 0.2 pH unit and a precision of 0.2 pH unit.

(6) The result of analysis of parameters under this regulation must be expressed using at least the same number of significant figures as for the associated parametric values in Part 1 of Schedule 1.

(7) For these purposes—

“limit of quantification” is to be calculated using an appropriate standard or sample, and may be obtained from the lowest calibration point on the calibration curve, excluding the blank; and

“measurement uncertainty” shall be estimated at the level of the parametric value, unless otherwise specified.

Authorisation of alternative methods of analysis

3.—(1) If the Department is satisfied that an alternative method of analysis is at least as reliable as a method of analysis prescribed by paragraph 2(2), it may authorise its use instead of the prescribed method.

(2) The Department shall provide the European Commission with relevant information concerning such methods authorised in paragraph 3(1) and their equivalence.

(3) Until 31 December 2019 the Department may use “trueness”, “precision” and “limit of detection” as specified in Table C in Part 2 of this Schedule (“Table C”) as alternative sets of performance characteristics to “limit of quantification” and “uncertainty of measurement” specified in paragraph 6 and Table B of this Schedule.

(4) For the purposes of this paragraph the method of analysis for each parameter specified in the first column of Table C must be capable of—

(a)measuring concentrations and values with the trueness and precision specified in the second and third columns of that table; and

(b)detecting the parameter at the limit of detection specified in the fourth column of that table.

(5) For hydrogen ion, a method of analysis must be capable at the time of use of measuring a value with a trueness of 0.2 pH unit and a precision of 0.2 pH unit.

(6) For these purposes—

“limit of detection” is to be calculated as—

(a)

three times the relative within-batch standard deviation of a natural sample containing a low concentration of the parameter; or

(b)

five times the relative within-batch standard deviation of a blank sample;

“precision” (the random error) is to be calculated as twice the standard deviation (within a batch and between batches) of the spread of results about the mean; and

“trueness” (the systematic error) is to be calculated as the difference between the mean value of the large number of repeated measurements and the true value.

(7) In the absence of an analytical method meeting the minimum performance criteria set out in sub-paragraph (3) and paragraph 2(3) the Department must ensure that monitoring is carried out using best available techniques not entailing excessive costs.

Laboratories

4.  The Department must ensure that the laboratory at which samples are analysed has a system of analytical quality control in accordance with EN ISO/IEC 17025 or other equivalent standards accepted at an international level and is subjected from time to time to checking by a person who is—

(a)not under the control of either the laboratory or the Department; and

(b)approved by the Department for that purpose.

Interpretation

5.  In this schedule—

“laboratory” includes any land at which samples are analysed for the purposes of these Regulations (including on-site analysis); and

“taking and analysing samples” includes taking, handling, transporting, storing and analysing samples.

PART 2Analytical Methods and Performance Characteristics

TABLE A

Prescribed methods of analysis

(1) Parameter(2) Method
Clostridium perfringens (including spores)EN ISO 14189
Coliform bacteriaEN ISO 9308-1 or EN ISO 9308-2
Colony count 22°C-enumeration of culturable microorganismsEN ISO 6222
EnterococciEN ISO 7899-2
Escherichia coli (E. coli)EN ISO 9308-1 or EN ISO 9308-2
Pseudomonas aeruginosaEN ISO 16266

TABLE B

Minimum performance characteristic: “uncertainty of measurement”

(1) Parameter(1)(2) Uncertainty of measurement (% of parametric value, except pH)(2)
(1)

Acrylamide, epichlorohydrin and vinyl chloride to be controlled by product specification.

(2)

Uncertainty of measurement is a non-negative parameter characterising the dispersion of the quantity values being attributed to a measurand, based on the information used. The performance criterion for measurement uncertainty (k = 2) is the percentage of the parametric value stated in the table or better. Measurement uncertainty must be estimated at the level of the parametric value, unless otherwise specified.

(3)

If the value of uncertainty of measurement cannot be met, the best available technique should be selected (up to 60%).

(4)

The method determines total cyanide in all forms.

(5)

Values for trueness, precision and uncertainty of measurement are expressed in pH units.

(6)

Reference method EN ISO 8467.

(7)

The performance characteristics for individual pesticides are given as an indication. Values for the uncertainty of measurement as low as 30% can be achieved for several pesticides, higher values up to 80% may be allowed for a number of pesticides.

(8)

The performance characteristics apply to individual substances, specified at 25% of the parametric value in Table B of Schedule 1.

(9)

The performance characteristics apply to individual substances, specified at 50% of the parametric value in Table B of Schedule 1.

(10)

The uncertainty of measurement should be estimated at the level of 3 mg/l of the total organic carbon. CEN 1484 Guidelines for the determination of total organic carbon and dissolved organic carbon must be used.

(11)

The uncertainty of measurement must be estimated at the level of 1.0 NTU (nephelometric turbidity units) in accordance with EN ISO 7027.

Aluminium25
Ammonium40
Antimony40
Arsenic30
Benzo(a)pyrene(3)50
Benzene40
Boron25
Bromate40
Cadmium25
Chloride15
Chromium30
Colour20
Conductivity20
Copper25
Cyanide(4)30
1,2-dichloroethane40
Fluoride20
Hydrogen ion concentration pH (expressed in pH units)(5)0.2
Iron30
Lead25
Manganese30
Mercury30
Nickel25
Nitrate15
Nitrite20
Oxidisability(6)50
Pesticides(7)30
Polycyclic aromatic hydrocarbons(8)50
Selenium40
Sodium15
Sulphate15
Tetrachloroethene(9)30
Tetrachloromethane30
Trichloroethene(9)40
Trihalomethanes: total(8)40
Total organic carbon(10)30
Turbidity(11)30

TABLE C

Minimum performance characteristics: trueness, precision and limit of detection- may be used until 31 December 2019

(1) Parameter(1)

(2) Trueness

(% of parametric value, except for pH)(2)

(3) Precision

(% of parametric value, except for pH)(3)

(4) Limit of detection

(% of parametric value, except for pH)(4)

(1)

Acrylamide, epichlorohydrin and vinyl chloride to be controlled by product specification.

(2)

Trueness is a measure of systematic error, i.e. the difference between the mean value of the large number of repeated measurements and the true value. Further specifications are those set out in ISO 5725.

(3)

Precision is a measure of random error and is usually expressed as the standard deviation (within and between batches) of the spread of results from the mean. Acceptable precision is twice the relative standard deviation. This term is further specified in ISO 5725.

(4)

Limit of detection is either three times the standard deviation within a batch of a natural sample containing a low concentration of the parameter; or five times the standard deviation of a blank sample (within a batch).

(5)

The method determines total cyanide in all forms.

(6)

Values for trueness, precision and uncertainty of measurement are expressed in pH units.

(7)

Reference method EN ISO 8467.

(8)

The performance characteristics for individual pesticides are given as an indication. Values for the uncertainty of measurement as low as 30% can be achieved for several pesticides, higher values up to 80 % may be allowed for a number of pesticides.

(9)

The performance characteristics apply to individual substances, specified at 25% of the parametric value in Table B of Schedule 1.

(10)

The performance characteristics apply to individual substances, specified at 50% of the parametric value in Table B of Schedule 1.

(11)

The performance characteristics apply to prescribed value 4 NTU.

(12)

The performance characteristics apply to prescribed value 1 NTU for water leaving surface water treatment works.

Aluminium101010
Ammonium101010
Antimony252525
Arsenic101010
Benzene252525
Benzo(a)pyrene252525
Boron101010
Bromate252525
Cadmium101010
Chloride101010
Chromium101010
Colour101010
Conductivity101010
Copper101010
Cyanide(5)101010
1,2-dichloroethane252510
Fluoride101010
Hydrogen ion concentration pH (expressed in pH units)(6)0.20.2
Iron101010
Lead101010
Manganese101010
Mercury201020
Nickel101010
Nitrate101010
Nitrite101010
Oxidisability(7)502510
Pesticides(8)252525
Polycyclic aromatic hydrocarbons(9)252525
Selenium101010
Sodium101010
Sulphate101010
Tetrachloroethene(10)252510
Tetrachloromethane202020
Trichloroethene(10)252510
Trihalomethanes: total(9)252510
Turbidity(11)101010
Turbidity(12)252525

PART 3Monitoring for Indicative Dose and Analytical Performance Characteristics

Monitoring for Compliance with the ID

6.  Screening strategy for gross alpha activity and gross beta activity (1) may be used to monitor for the parametric indicator value for indicative dose.

If the gross alpha activity is less than 0.1 Bq/l and the gross beta activity is less than 1.0 Bq/l, it may be assumed that the total indicative dose is less than 0.1 mSv and radiological investigation is not needed unless it is known from other sources of information that specific radionuclides are present in water that are liable to cause an excess of 0.1 mSv.

If the gross alpha activity exceeds 0.1Bq/l or the gross beta activity exceeds 1.0Bq/l, analysis for specific radionuclides is required.

The radionuclides to be measured must be based on all relevant information about likely sources of radioactivity.

Calculation of the ID

7.  The ID must be calculated from the measured radionuclide concentrations and the dose coefficients laid down in Annex III, Table A of Directive 96/29/Euratom(2) or more recent information recognised by the Department, on the basis of the annual intake of water (730l for adults).

Where the following formula is satisfied, it can be assumed that the ID is less than the parametric value of 0.1mSv and no further investigation is required.

where

  • Ci(obs) = observed concentration of radionuclide i

  • Ci(der) = derived concentration of radionuclide i (see Table D)

  • n = number of radionuclides detected.

TABLE D
Derived concentrations for radioactivity in water intended for human consumption
OriginRadionuclide(1)Derived concentration (Bq/1)
(1)

This table includes values for the most common natural and artificial radionuclides; these are precise values, calculated for a dose of 0.1mSV, an annual intake of 730 litres and using the dose coefficients laid down in Annex III, Table A of Directive 96/29/Euratom; derived concentration for other radionuclides can be calculated on the same basis, and values can be updated on the basis of more recent information recognised by the Department.

(2)

This allows only for the radiological properties of uranium, not for its chemical toxicity.

NaturalU-238(2)3.0
U-234(2)2.8
Ra-2260.5
Ra-2280.2
Pb-2100.2
Po-2100.1
ArtificialC-14240
Sr-904.9
Pu-239 / Pu-2400.6
Am-2410.7
Co-6040
Cs-1347.2
Cs-13711
I-1316.2

Performance characteristics and method of analysis.

8.  For the following parameters and radionuclides, the method of analysis used must, as a minimum be capable of measuring activity concentrations with a limit of detection specified below in Table E:

TABLE E
Parameters and radiouclidesLimit of detection(1) (2)
(1)

The limit of detection must be calculated according to the ISO standard 11929:2010 entitled “Determination of the characteristic limits (decision threshold, detection limit and limits of the confidence interval) for measurements of ionising radiation - Fundamentals and application”, with probabilities of errors of 1st and 2nd kind of 0.05 each.

(2)

Measurement uncertainties must be calculated and reported as complete standard uncertainties, or as expanded standard uncertainties with an expansion factor of 1.96, according to the ISO IEC Guide 98-3:2008 entitled “Guide to the expression of uncertainty in measurement”.

(3)

The limit of detection for tritium and for radon is 10% of the corresponding parametric value of 100 Bg/l.

(4)

The limit of detection for gross alpha activity and gross beta activities is 40% of the screening values of 0.1 Bq/l and 1.0 Bq/l respectively.

(5)

This limit of detection applies only to initial screening for indicative dose for a new water source. If initial checking indicates that it is unlikely that Ra-228 exceeds 20% of the derived concentration, the limit of detection may be increased to 0.08 Bq/l for routine Ra-228 nuclide specific measurements, until a subsequent re-check is required.

Tritium10 Bg/l(3)
Radon10 Bg/l(3)
gross alpha activity0.04 Bg/l(4)
gross beta activity0.4 Bg/l(4)
U-2380.02 Bg/l
U-2340.02 Bg/l
Ra-2260.04 Bg/l
Ra-2280.02 Bg/l(5)
Pb-2100.02 Bg/l
Po-2100.01 Bg/l
C-1420 Bg/l
Sr-900.4 Bg/l
Pu-239/Pu-2400.04 Bg/l
Am-2410.06 Bg/l
Co-600.5 Bg/l
Cs-1340.5 Bg/l
Cs-1370.5 Bg/l
I-1310.5 Bg/l
(1)

Where appropriate gross beta activity may be replaced by residual beta activity after subtraction of the K-40 activity concentration.

(2)

O.J. No. L159, 29.6.96, P. 27

Back to top

Options/Help

Print Options

Close

Legislation is available in different versions:

Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.

Original (As Enacted or Made):The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.

Close

Opening Options

Different options to open legislation in order to view more content on screen at once

Close

Explanatory Memorandum

Explanatory Memorandum sets out a brief statement of the purpose of a Statutory Rule and provides information about its policy objective and policy implications. They aim to make the Statutory Rule accessible to readers who are not legally qualified and accompany any Northern Ireland Statutory Rule or Draft Northern Ireland Statutory Rule laid before the UK Parliament during the suspension of the Northern Ireland Assembly.

Close

More Resources

Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as enacted version that was used for the print copy
  • lists of changes made by and/or affecting this legislation item
  • confers power and blanket amendment details
  • all formats of all associated documents
  • correction slips
  • links to related legislation and further information resources
Close

More Resources

Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as made version that was used for the print copy
  • correction slips

Click 'View More' or select 'More Resources' tab for additional information including:

  • lists of changes made by and/or affecting this legislation item
  • confers power and blanket amendment details
  • all formats of all associated documents
  • links to related legislation and further information resources