The Private Water Supplies Regulations (Northern Ireland) 2017

Sampling

This section has no associated Explanatory Memorandum

1.—(1) The Department must monitor for a Group A parameter in accordance with this Part.

(2) “Monitoring for a Group A parameter” means sampling for—

(a)each parameter listed in column 1 of Table 1 of this Schedule in the circumstances listed in the entry which corresponds with that parameter in column 2 of Table 1 of this Schedule; and

(b)any other parameter which may be identified as relevant by the Department in the monitoring programme.

TABLE 1
Group A parameters
(1) Parameter(2) Circumstances
(1)

A supply which consists of both groundwater and surface water shall be deemed to be a supply which consists only of surface water.

Aluminium(1)If used as water treatment chemicals or where the water originates from, or is influenced by, surface waters
AmmoniumWhere chloramination is practised
Coliform bacteriaIn all supplies
Colony CountsIn all supplies
ColourIn all supplies
ConductivityIn all supplies
Disinfectant residualWhen disinfection treatment is practised
Escherichia coli (E. coli)In all supplies
Indicative DoseWhere there is treatment in place to reduce the level of radionuclides in water intended for human consumption.
Iron(1)If used as water treatment chemicals or where the water originates from, or is influenced by, surface waters
Manganese(1)Where the water originates from, or is influenced by, surface waters
NitriteWhere chloramination is practised
OdourIn all supplies
pH (Hydrogen ion)In all supplies
RadonWhere there is treatment in place to reduce the level of radionuclides in water intended for human consumption.
TasteIn all supplies
TritiumWhere there is treatment in place to reduce the level of radionuclides in water intended for human consumption.
TurbidityIn all supplies