xmlns:atom="http://www.w3.org/2005/Atom"

SCHEDULE 1Prescribed Concentrations and Values

PART 2Indicator Parameters

TABLE C

Prescribed concentrations and values

ParameterParametric valueUnit
(1)

The water must not be aggressive.

(2)

Excluding tritium, potassium-40, radon and radon decay products.

(3)

Where treatment to reduce the level of radionuclides in water intended for human consumption has been taken, monitoring must be carried out under Schedule 3 Part 1 to ensure efficacy of treatment.

(4)

If the gross alpha activity exceeds 0.1Bq/l or the gross beta activity exceeds 1.0Bq/l analysis for specific radionuclides is required.

(5)

If tritium concentration exceeds its parametric value an investigation (which may include analysis) of the presence of other artificial radionuclides must be carried out.

(6)

Remedial action is deemed to be justified on radiological ground without further consideration, where radon exceeds 1,000Bq/l.

(7)

Only in the case of surface water treatment where the parametric value should be strived for the water ex-treatment works.

Ammonium0.50mg/l
Chloride(1)250mg/l

Clostridium perfringens

(including spores)

0number/100 ml
Coliform bacteria0Number/100ml
Colony count 22 °CNo abnormal changenumber/1 ml
Conductivity(1)2500μS/cm at 20 °C
Hydrogen ion concentration(1)≥ 6.5 and ≤ 9.5pH units
Indicative Dose (for radioactivity)(2) (3) (4)0.10mSv
Sulphate(1)250mg/l
Radon (for radioactivity)(3) (6)100Bq/l
Total organic carbonNo abnormal changemg/l
Tritium (for radioactivity)(3) (5)100Bq/l
Turbidity(7)1NTU