xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"

PART IIN.I.REQUIREMENTS

Restriction on installation etc. of water fittingsN.I.

3.—(1) No person shall—

(a)install a water fitting to convey or receive water supplied by a water undertaker, or alter, disconnect or use such a water fitting; or

(b)cause or permit such a water fitting to be installed, altered, disconnected or used,

in contravention of the following provisions of this Part.

(2) No water fitting shall be installed, connected, arranged or used in such a manner that it causes or is likely to cause—

(a)waste, misuse, undue consumption or contamination of water supplied by a water undertaker; or

(b)the erroneous measurement of water supplied by a water undertaker.

(3) No water fitting shall be installed, connected, arranged or used which by reason of being damaged, worn or otherwise faulty, causes or is likely to cause—

(a)waste, misuse, undue consumption or contamination of water supplied by a water undertaker; or

(b)the erroneous measurement of water supplied by a water undertaker.

Commencement Information

I1Reg. 3 in operation at 3.8.2009, see reg. 1(1)

Requirements for water fittings etc.N.I.

4.—(1) Every water fitting shall—

(a)be of an appropriate quality and standard; and

(b)be suitable for the circumstances in which it is used.

(2) For the purposes of this regulation, a water fitting is of an appropriate quality or standard only if—

F1(a). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F2(b). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(c)it conforms to an appropriate British Standard or some other national specification F3... which provides an equivalent level of protection and performance; or

(d)it conforms with the terms of a specification approved by the Secretary of State or the National Assembly of Wales under The Water Supply (Water Fittings) Regulations 1999.

(3) Every water fitting shall comply with the requirements of Schedule 2 as it applies to that fitting.

(4) Where any requirement of Schedule 2 relates to a water system, every water fitting which forms part of that system shall be fitted or, as the case may be, altered or replaced so as to comply with that requirement.

(5) Every water fitting shall be installed, connected, altered, repaired or disconnected in a workmanlike manner.

(6) For the purposes of this regulation, a water fitting is installed, connected, altered, repaired or disconnected in a workmanlike manner only if the work is carried out so as to conform—

(a)to an appropriate British StandardF4... or some other national specification F5... which provides an equivalent level of protection and performance;

(b)to a specification approved by the Secretary of State or the National Assembly of Wales under The Water Supply (Water Fittings) Regulations 1999; or

(c)to a method of installation approved by the water undertaker.

NotificationN.I.

5.—(1) Subject to paragraph (2), any person who proposes to install a water fitting in connection with any of the operations listed in the Table below—

(a)shall give notice to the water undertaker that he proposes to begin work;

(b)shall not begin that work without the consent of the water undertaker which shall not be withheld unreasonably; and

(c)shall comply with any conditions to which the water undertaker’s consent is subject.

Table
1.

The erection of a building or other structure, not being a pond or swimming pool.

2.

The extension or alteration of a water system on any premises other than a house.

3.

A material change of use of any premises.

4.

The installation of—

(a)

a bath having a capacity, as measured to the centre line of overflow, of more than 230 litres;

(b)

a bidet or WC with an ascending spray or flexible hose;

(c)

a single shower unit (which may consist of one or more shower heads within a single unit) which is of a type which conforms to a specification approved by the Secretary of State or the National Assembly of Wales under The Water Supply (Water Fittings) Regulations 1999, not being a drench shower installed for reasons of safety or health, connected directly or indirectly to a supply pipe;

(d)

a pump or booster drawing more than 12 litres per minute, connected directly or indirectly to a supply pipe; or a pump delivery pipe drawing water from a supply pipe;

(e)

a unit which incorporates reverse osmosis;

(f)

a water treatment unit which produces a waste water discharge or which requires the use of water for regeneration or cleaning;

(g)

a type BA device or other mechanical device for protection against a fluid which is in fluid category 4;

(h)

a garden watering system unless designed to be operated by hand;

(i)

any water system laid outside a building and either less than 750mm or more than 1350mm below ground level;

(j)

greywater, recycled water, reclaimed water and rainwater harvesting systems;

(k)

water systems for fire fighting, including domestic sprinklers;

(l)

a flexible shower hose or other flexible outlet for use in conjunction with a WC; or

(m)

a ‘shower-toilet’ or ‘bidet- toilet’ where, either as part of the WC itself or as an addition or adaptation of it, a stream of water is provided from below the spillover level of the WC pan for personal cleansing.

5.

The construction of ponds or swimming pools with a capacity, individually or together, greater than 10,000 litres which are designed to be replenished by automatic means and are to be filled with water supplied by a water undertaker.

(2) This regulation does not apply to the installation by an approved contractor of a water fitting falling within paragraph 2, 4(b), 4(l) or 4(m) in the Table.

(3) The notice required by paragraph (1) shall include or be accompanied by—

(a)the name and address of the person giving the notice, and (if different) the name and address of the person on whom notice may be served under paragraph (4);

(b)a description of the proposed work or material change of use; and

(c)particulars of the location of the premises to which the proposal relates, and the use or intended use of those premises;

(d)except in the case of a fitting falling within paragraph 4(a), (c), (h) or 5 in the table—

(i)a plan of those parts of the premises to which the proposal relates, and

(ii)a diagram showing the pipework and fitting to be installed; and

(e)where the work is to be carried out by an approved contractor, the name of the contractor.

(4) The water undertaker may withhold consent required under paragraph (1), or grant it subject to conditions, by a notice given before the expiry of the period of ten working days commencing with the day on which notice under that paragraph was given.

(5) If no notice is given by the water undertaker within the period mentioned in paragraph (4), the consent required under paragraph (1) shall be deemed to have been granted unconditionally.

Commencement Information

I3Reg. 5 in operation at 3.8.2009, see reg. 1(1)

Contractor’s certificateN.I.

6.—(1) Where a water fitting is installed, altered, connected or disconnected by an approved contractor, the contractor shall upon completion of the work furnish a signed certificate stating whether the water fitting complies with the requirements of these Regulations to the person who commissioned the work.

(2) In the case of a fitting for which notice is required under regulation 5(1), the contractor shall send a copy of the certificate to the water undertaker.

Commencement Information

I4Reg. 6 in operation at 3.8.2009, see reg. 1(1)