xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"
For each ecodesign requirement, the moment from which it applies is specified below. Unless a requirement is superseded or this is otherwise specified, it shall continue to apply together with the requirements introduced at later stages.
One year after the entry into force of this Regulation:
Double capped fluorescent lamps of 16 mm and 26 mm diameter (T5 and T8 lamps) shall have at least the rated luminous efficacies as specified in Table 1 at 25 °C.
[F1Spiral-shaped double capped fluorescent lamps of all diameters equal to or larger than 16 mm (T5) shall comply with the requirements set out in Table 5 for T9 circular lamps.]
Textual Amendments
F1 Inserted by Commission Regulation (EU) No 347/2010 of 21 April 2010 amending Commission Regulation (EC) No 245/2009 as regards the ecodesign requirements for fluorescent lamps without integrated ballast, for high intensity discharge lamps, and for ballasts and luminaires able to operate such lamps (Text with EEA relevance).
Rated minimum efficacy values for T8 and T5 lamps
T8 (26 mm Ø) | T5 (16 mm Ø)High Efficiency | T5 (16 mm Ø)High Output | |||
---|---|---|---|---|---|
Nominal wattage (W) | Rated luminous efficacy (lm/W), 100 h initial value | Nominal wattage (W) | Rated luminous efficacy (lm/W), 100 h initial value | Nominal wattage (W) | Rated luminous efficacy (lm/W), 100 h initial value |
15 | 63 | 14 | 86 | 24 | 73 |
18 | 75 | 21 | 90 | 39 | 79 |
25 | 76 | 28 | 93 | 49 | 88 |
30 | 80 | 35 | 94 | 54 | 82 |
36 | 93 | 80 | 77 | ||
38 | 87 | ||||
58 | 90 | ||||
70 | 89 |
Single capped fluorescent lamps shall have the following rated luminous efficacies at 25 °C.
In case the nominal wattages or lamp shapes are different from those listed in tables 2 to 5: lamps must reach the luminous efficacy of the nearest equivalent in terms of wattage and shape. If the nominal wattage is at equal distance from two wattages in the table, it shall conform to the higher efficacy of the two. If the nominal wattage is higher than the highest wattage in the table, it shall conform to the efficacy of that highest wattage.
Rated minimum efficacy values for single capped fluorescent lamps working on electromagnetic and electronic ballast
Textual Amendments
F2 Substituted by Commission Regulation (EU) No 347/2010 of 21 April 2010 amending Commission Regulation (EC) No 245/2009 as regards the ecodesign requirements for fluorescent lamps without integrated ballast, for high intensity discharge lamps, and for ballasts and luminaires able to operate such lamps (Text with EEA relevance).
Rated minimum efficacy values for single capped fluorescent lamps, working only on electronic ballast
Rated minimum efficacy values for single capped fluorescent lamps with square shape or (very) high output
Rated minimum efficacy values for T9 and T5 Circular lamps
The required luminous efficacy at 25 °C may be lower than required in the tables above in the following cases:
Deduction percentages for rated minimum efficacy values for fluorescent lamps with high colour temperature and/or high colour rendering and/or second lamp envelope and/or long life
Lamp parameter | Deduction from luminous efficacy at 25 °C |
---|---|
Tc ≥ 5 000 K | – 10 % |
95 ≥ Ra > 90 | – 20 % |
Ra > 95 | – 30 % |
Second lamp envelope | – 10 % |
Lamp Survival Factor ≥ 0,50 after 40 000 burning hours | – 5 %] |
The indicated deductions are cumulative.
Single and double capped fluorescent lamps that do not have their optimum temperature at 25 °C must still comply at their optimum temperature with the luminous efficacy requirements as set out in the tables above.
Three years after the entry into force of this Regulation, the following efficacy requirements shall apply to fluorescent lamps without integrated ballast and high-intensity discharge lamps.
The requirements applicable to double capped fluorescent lamps 26 mm in diameter (T8) during the first stage shall apply to all double capped fluorescent lamps of other diameters than those covered in the first stage.
These lamps must conform to the minimum efficacy of the T8 lamp which is their nearest equivalent with regards to wattage. If the nominal wattage is higher than the highest wattage in the table, it shall conform to the efficacy of that highest wattage.
[F2The corrections (Table 6) and the specific requirements for spiral-shaped double capped fluorescent lamps defined for the first stage shall continue to apply.]
Lamps with Tc ≥ 5 000 K or equipped with a second lamp envelope shall fulfil at least 90 % of the applicable lamp efficacy requirements in tables 7, 8 and 9.
High Pressure Sodium lamps with Ra ≤ 60 shall have at least the rated luminous efficacies in Table 7:
Rated minimum efficacy values for high pressure sodium lamps with Ra ≤ 60]
Nominal Lamp wattage [W] | Rated Lamp Efficacy [lm/W] — Clear lamps | Rated Lamp Efficacy [lm/W] — Not clear lamps |
---|---|---|
W ≤ 45 | ≥ 60 | ≥ 60 |
45 < W ≤ 55 | ≥ 80 | ≥ 70 |
55 < W ≤ 75 | ≥ 90 | ≥ 80 |
75 < W ≤ 105 | ≥ 100 | ≥ 95 |
105 < W ≤ 155 | ≥ 110 | ≥ 105 |
155 < W ≤ 255 | ≥ 125 | ≥ 115 |
255 < W ≤ 605 | ≥ 135 | ≥ 130 |
The requirements in Table 7 shall apply to high pressure sodium retrofit lamps designed to operate on high pressure mercury vapour lamp control gear only 6 years after the entry into force of this Regulation.
Metal halide lamps with Ra ≤ 80 and high pressure sodium lamps with Ra > 60 shall have at least the rated luminous efficacies in Table 8:
Rated minimum efficacy values for Metal Halide Lamps with Ra ≤ 80 and for high pressure sodium lamps with Ra > 60]
Nominal Lamp Wattage [W] | Rated Lamp Efficacy [lm/W] — Clear lamps | Rated Lamp Efficacy [lm/W] — Not clear lamps |
---|---|---|
W ≤ 55 | ≥ 60 | ≥ 60 |
55 < W ≤ 75 | ≥ 75 | ≥ 70 |
75 < W ≤ 105 | ≥ 80 | ≥ 75 |
105 < W ≤ 155 | ≥ 80 | ≥ 75 |
155 < W ≤ 255 | ≥ 80 | ≥ 75 |
255 < W ≤ 405 | ≥ 85 | ≥ 75 |
Six years after the entry into force of this Regulation, other high intensity discharge lamps shall have at least the rated luminous efficacies in Table 9:
Rated minimum efficacy values for other high intensity discharge lamps
Nominal Lamp wattage [W] | Rated Lamp Efficacy [lm/W] |
---|---|
W ≤ 40 | 50 |
40 < W ≤ 50 | 55 |
50 < W ≤ 70 | 65 |
70 < W ≤ 125 | 70 |
125 < W | 75 |
Eight years after the entry into force of this Regulation:
[F2Fluorescent lamps without integrated ballast shall be able to operate with ballasts of energy efficiency class A2 or more efficient ballasts in accordance with point 2.2 of Annex III. In addition they may also operate with ballasts of less efficient classes than A2.]
Metal halide lamps shall have at least the rated luminous efficacies in Table 10:
Rated minimum efficacy values for metal halide lamps (third stage)
Nominal Lamp wattage (W) | Rated Lamp Efficacy (lm/W) — Clear lamps | Rated Lamp Efficacy (lm/W) — Not clear lamps |
---|---|---|
W ≤ 55 | ≥ 70 | ≥ 65 |
55 < W ≤ 75 | ≥ 80 | ≥ 75 |
75 < W ≤ 105 | ≥ 85 | ≥ 80 |
105 < W ≤ 155 | ≥ 85 | ≥ 80 |
155 < W ≤ 255 | ≥ 85 | ≥ 80 |
255 < W ≤ 405 | ≥ 90 | ≥ 85 |
Lamps equipped with Tc ≥ 5 000 K or with a second lamp envelope shall fulfil at least 90 % of the applicable lamp efficacy requirements.
One year after the entry into force of this Regulation:
Fluorescent lamps without integrated ballast covered by the requirements of Annex III.1.1.A shall have a colour rendering index (Ra) of at least 80.
Three years after the entry into force of this Regulation:
Fluorescent lamps without integrated ballast shall have a colour rendering index (Ra) of at least 80. They shall have at least the lamp lumen maintenance factors in Table 11:
Lamp lumen maintenance factors for single and double capped fluorescent lamps — Stage 2
Lamp lumen maintenance factor | Burning hours | |||
---|---|---|---|---|
Lamp types | 2 000 | 4 000 | 8 000 | 16 000 |
Double-Capped Fluorescent lamps operating on non-high frequency ballasts | 0,95 | 0,92 | 0,9 | — |
T8 Double-Capped Fluorescent lamps on high frequency ballast with warmstart | 0,96 | 0,92 | 0,91 | 0,9 |
Other Double-Capped Fluorescent lamps on high frequency ballast with warmstart | 0,95 | 0,92 | 0,9 | 0,9 |
Circular Single-Capped Fluorescent lamps operating on non-high frequency ballasts, T8 U-shaped double-capped fluorescent lamps and spiral-shaped double capped fluorescent lamps of all diameters equal to or larger than 16 mm (T5) | 0,8 | 0,74 | — | — |
0,72 at 5 000 burning hours | ||||
Circular Single-Capped Fluorescent lamps operating on high frequency ballasts | 0,85 | 0,83 | 0,8 | — |
0,75 at 12 000 burning hours | ||||
Other Single-Capped Fluorescent lamps operating on non-high frequency ballasts | 0,85 | 0,78 | 0,75 | — |
Other Single-Capped Fluorescent lamps on high frequency ballast with warmstart | 0,9 | 0,84 | 0,81 | 0,78] |
[F1The following cumulative deductions shall be applied to the values in Table 11:
Deduction percentages for fluorescent lamp lumen maintenance requirements
Lamp parameter | Deduction from lamp lumen maintenance requirement |
---|---|
Lamps with 95 ≥ Ra > 90 | At burning hours ≤ 8 000 h: – 5 % At burning hours > 8 000 h: – 10 % |
Lamps with Ra > 95 | At burning hours ≤ 4 000 h: – 10 % At burning hours > 4 000 h: – 15 % |
Lamps with a colour temperature ≥ 5 000 K | – 10 %] |
Fluorescent lamps without integrated ballast shall have at least the lamp survival factors in Table 12:
Lamp survival factors for single and double capped fluorescent lamps — Stage 2
Lamp survival factor | Burning hours | |||
---|---|---|---|---|
Lamp types | 2 000 | 4 000 | 8 000 | 16 000 |
Double-Capped Fluorescent lamps operating on non-high frequency ballasts | 0,99 | 0,97 | 0,9 | — |
Double-Capped Fluorescent lamps on high frequency ballast with warmstart | 0,99 | 0,97 | 0,92 | 0,9 |
Circular Single-Capped Fluorescent lamps operating on non-high frequency ballasts, T8 U-shaped double-capped fluorescent lamps and spiral-shaped double capped fluorescent lamps of all diameters equal to or larger than 16 mm (T5) | 0,98 | 0,77 | — | — |
0,50 at 5 000 burning hours | ||||
Circular Single-Capped Fluorescent lamps operating on high frequency ballasts | 0,99 | 0,97 | 0,85 | — |
0,50 at 12 000 burning hours | ||||
Other Single-Capped Fluorescent lamps operating on non-high frequency ballasts | 0,98 | 0,9 | 0,5 | — |
Other Single-Capped Fluorescent lamps on high frequency ballast with warmstart | 0,99 | 0,98 | 0,88 | —] |
[F3High pressure sodium lamps with lamp efficacy requirements shall have at least the lamp lumen maintenance factors and lamp survival factors in Table 13:
Textual Amendments
F3 Substituted by Commission Regulation (EU) 2015/1428 of 25 August 2015 amending Commission Regulation (EC) No 244/2009 with regard to ecodesign requirements for non-directional household lamps and Commission Regulation (EC) No 245/2009 with regard to ecodesign requirements for fluorescent lamps without integrated ballast, for high intensity discharge lamps, and for ballasts and luminaires able to operate such lamps and repealing Directive 2000/55/EC of the European Parliament and of the Council and Commission Regulation (EU) No 1194/2012 with regard to ecodesign requirements for directional lamps, light emitting diode lamps and related equipment (Text with EEA relevance).
Lamp lumen maintenance factors & lamp survival factors for high pressure sodium lamps — Stage 2
High pressure sodium lamp category and burning hours for measurement | Lamp lumen maintenance factor | Lamp survival factor | |
---|---|---|---|
P ≤ 75 W LLMF and LSF measured at 12 000 burning hours | Ra ≤ 60 | > 0,80 | > 0,90 |
Ra > 60 | > 0,75 | > 0,75 | |
all retrofit lamps designed to operate on high pressure mercury vapour lamp ballast | > 0,75 | > 0,80 | |
P > 75 W ≤ 605 W LLMF and LSF measured at 16 000 burning hours | Ra ≤ 60 | > 0,85 | > 0,90 |
Ra > 60 | > 0,70 | > 0,65 | |
all retrofit lamps designed to operate on high pressure mercury vapour lamp ballast | > 0,75 | > 0,55 |
The requirements in Table 13 for retrofit lamps designed to operate on high pressure mercury vapour lamp ballast shall be applicable until 6 years after the entry into force of this Regulation.]
Eight years after the entry into force of this Regulation:
Metal halide lamps with lamp efficacy requirements shall have at least the lamp lumen maintenance factors and lamp survival factors in Table 14:
Lamp lumen maintenance factors and lamp survival factors for metal halide lamps — Stage 3
Burning Hours | Lamp lumen maintenance factor | Lamp survival factor |
---|---|---|
12 000 | > 0,80 | > 0,80] |
One year after the entry into force of this Regulation, manufacturers shall provide at least the following information on free-access websites and in other forms they deem appropriate for each of their fluorescent lamps without integrated ballast and each of their high intensity discharge lamps. That information shall also be contained in the technical documentation file drawn up for the purposes of conformity assessment pursuant to Article 8 of Directive 2005/32/EC.
Nominal and rated lamp wattage.
Nominal and rated lamp luminous flux.
Rated lamp efficacy at 100 h in standard conditions (25 °C, for T5 lamps at 35 °C). For fluorescent lamps both at 50 Hz (mains frequency) operation (where applicable) and at High Frequency (> 50 Hz) operation (where applicable) for the same rated luminous flux in all cases, indicating for High Frequency operation the calibration current of the test conditions and/or the rated voltage of the HF generator with the resistance. It shall be stated in a conspicuous manner that the power dissipated by auxiliary equipment such as ballasts is not included in the power consumed by the source.
Rated lamp Lumen Maintenance Factor at 2 000 h, 4 000 h, 6 000 h, 8 000 h, 12 000 h, 16 000 h and 20 000 h (up to 8 000 h only for new lamps on the market where no data is yet available), indicating which operation mode of the lamp was used for the test if both 50 Hz and High Frequency operation are possible.
Rated lamp Survival Factor at 2 000 h, 4 000 h, 6 000 h, 8 000 h, 12 000 h, 16 000 h and 20 000 h (up to 8 000 h only for new lamps on the market where no data is yet available), indicating which operation mode of the lamp was used for the test if both 50 Hz and High Frequency operation are possible.
lamp mercury content as X.X mg.
Colour Rendering Index (Ra) of the lamp.
Colour temperature of the lamp.
[F2Ambient temperature inside the luminaire at which the lamp was designed to maximise its luminous flux. If this temperature is equal to or lower than 0 °C or equal to or higher than 50 °C, it shall be stated that the lamp is not suitable for indoor use at standard room temperatures.]
[F1For fluorescent lamps without integrated ballast, the energy efficiency index(es) of ballasts as defined in Table 17 with which the lamp can operate.]
Multiwattage ballasts shall comply with the requirements below according to each wattage on which they operate.
One year after this Regulation comes into force:
The minimum energy efficiency index class shall be B2 for ballasts covered by table 17 in Annex III.2.2, A3 for the ballasts covered by table 18, and A1 for dimmable ballasts covered by table 19.
At the dimming position corresponding to 25 % of the lumen output of the operated lamp, the input power (Pin) of the lamp-ballast circuit shall not exceed:
Pin < 50 % * PLrated/ηballast
Where PLrated is the rated lamp power and ηballast is the minimum energy efficiency limit of the respective EEI class.
The power consumption of the fluorescent lamp ballasts shall not exceed 1,0 W when operated lamps do not emit any light in normal operating conditions and when other possible connected components (network connections, sensors etc.) are disconnected. If they cannot be disconnected, their power shall be measured and deducted from the result.
Three years after the implementing measure comes into force:
Ballasts for high intensity discharge lamps shall have the efficiency described in Table 15.
Minimum efficiency for ballasts for high intensity discharge lamps — Stage 2
Nominal lamp wattage (P)W | Minimum ballast efficiency (ηballast)% |
---|---|
P ≤ 30 | 65 |
30 < P ≤ 75 | 75 |
75 < P ≤ 105 | 80 |
105 < P ≤ 405 | 85 |
P > 405 | 90 |
The power consumption of ballasts used with fluorescent lamps without integrated ballast shall not exceed 0,5 W when operated lamps do not emit any light in normal operating conditions. This requirement shall apply to ballasts when other possible connected components (network connections, sensors etc.) are disconnected. If they cannot be disconnected, their power shall be measured and deducted from the result.
Eight years after this Regulation comes into force:
Ballasts for fluorescent lamps without integrated ballast shall have the efficiency:
ηballast ≥ EBbFL
where EBbFL is defined in Annex II.3.g
Ballasts for high intensity discharge lamps shall have the efficiency described in Table 16.
Minimum efficiency for ballasts for high intensity discharge lamps — Stage 3
Nominal lamp wattage (P)W | Minimum ballast efficiency (ηballast)% |
---|---|
P ≤ 30 | 78 |
30 < P ≤ 75 | 85 |
75 < P ≤ 105 | 87 |
105 < P ≤ 405 | 90 |
P > 405 | 92 |
Manufacturers of ballasts shall provide at least the following information on free-access websites and in other forms they deem appropriate for each of their ballast models. That information shall also be affixed in a distinct and durable form to the ballast. It shall also be contained in the technical documentation file drawn up for the purposes of conformity assessment pursuant to Article 8 of Directive 2005/32/EC.
One year after the entry into force of this Regulation:
for ballasts for fluorescents lamps, an energy efficiency index (EEI) class shall be provided as defined below.
‘Energy efficiency index’ (EEI) means a classification system of ballasts for fluorescent lamps without integrated ballasts in classes according to efficiency limit values. The classes for non-dimmable ballasts are (in descending order of efficiency) A2 BAT, A2, A3, B1, B2 and for dimmable ballasts A1 BAT and A1.
Table 17 contains the EEI classes for ballasts which are designed to operate the lamps mentioned in the table or other lamps which are designed to be operated by the same ballasts as the lamps mentioned in the table (meaning that the data of the reference ballast is equal).
Energy efficiency index requirements for non-dimmable ballasts for fluorescent lamps
LAMP DATA | BALLAST EFFICIENCY (Plamp/Pinput) | ||||||||
---|---|---|---|---|---|---|---|---|---|
Non-dimmable | |||||||||
Lamp type | Nominal Wattage | ILCOS CODE | Rated/typical wattage | A2 BAT | A2 | A3 | B1 | B2 | |
50 Hz | HF | ||||||||
W | W | W | |||||||
T8 | 15 | FD-15-E-G13-26/450 | 15 | 13,5 | 87,8 % | 84,4 % | 75,0 % | 67,9 % | 62,0 % |
T8 | 18 | FD-18-E-G13-26/600 | 18 | 16 | 87,7 % | 84,2 % | 76,2 % | 71,3 % | 65,8 % |
T8 | 30 | FD-30-E-G13-26/900 | 30 | 24 | 82,1 % | 77,4 % | 72,7 % | 79,2 % | 75,0 % |
T8 | 36 | FD-36-E-G13-26/1200 | 36 | 32 | 91,4 % | 88,9 % | 84,2 % | 83,4 % | 79,5 % |
T8 | 38 | FD-38-E-G13-26/1050 | 38,5 | 32 | 87,7 % | 84,2 % | 80,0 % | 84,1 % | 80,4 % |
T8 | 58 | FD-58-E-G13-26/1500 | 58 | 50 | 93,0 % | 90,9 % | 84,7 % | 86,1 % | 82,2 % |
T8 | 70 | FD-70-E-G13-26/1800 | 69,5 | 60 | 90,9 % | 88,2 % | 83,3 % | 86,3 % | 83,1 % |
TC-L | 18 | FSD-18-E-2G11 | 18 | 16 | 87,7 % | 84,2 % | 76,2 % | 71,3 % | 65,8 % |
TC-L | 24 | FSD-24-E-2G11 | 24 | 22 | 90,7 % | 88,0 % | 81,5 % | 76,0 % | 71,3 % |
TC-L | 36 | FSD-36-E-2G11 | 36 | 32 | 91,4 % | 88,9 % | 84,2 % | 83,4 % | 79,5 % |
TCF | 18 | FSS-18-E-2G10 | 18 | 16 | 87,7 % | 84,2 % | 76,2 % | 71,3 % | 65,8 % |
TCF | 24 | FSS-24-E-2G10 | 24 | 22 | 90,7 % | 88,0 % | 81,5 % | 76,0 % | 71,3 % |
TCF | 36 | FSS-36-E-2G10 | 36 | 32 | 91,4 % | 88,9 % | 84,2 % | 83,4 % | 79,5 % |
TC-D / DE | 10 | FSQ-10-E-G24q=1 FSQ-10-I-G24d=1 | 10 | 9,5 | 89,4 % | 86,4 % | 73,1 % | 67,9 % | 59,4 % |
TC-D / DE | 13 | FSQ-13-E-G24q=1 FSQ-13-I-G24d=1 | 13 | 12,5 | 91,7 % | 89,3 % | 78,1 % | 72,6 % | 65,0 % |
TC-D / DE | 18 | FSQ-18-E-G24q=2 FSQ-18-I-G24d=2 | 18 | 16,5 | 89,8 % | 86,8 % | 78,6 % | 71,3 % | 65,8 % |
TC-D / DE | 26 | FSQ-26-E-G24q=3 FSQ-26-I-G24d=3 | 26 | 24 | 91,4 % | 88,9 % | 82,8 % | 77,2 % | 72,6 % |
TC-T / TE | 13 | FSM-13-E-GX24q=1 FSM-13-I-GX24d=1 | 13 | 12,5 | 91,7 % | 89,3 % | 78,1 % | 72,6 % | 65,0 % |
TC-T / TE | 18 | FSM-18-E-GX24q=2 FSM-18-I-GX24d=2 | 18 | 16,5 | 89,8 % | 86,8 % | 78,6 % | 71,3 % | 65,8 % |
TC-T / TC-TE | 26 | FSM-26-E-GX24q=3 FSM-26-I-GX24d=3 | 26,5 | 24 | 91,4 % | 88,9 % | 82,8 % | 77,5 % | 73,0 % |
TC-DD / DDE | 10 | FSS-10-E-GR10q FSS-10-L/P/H-GR10q | 10,5 | 9,5 | 86,4 % | 82,6 % | 70,4 % | 68,8 % | 60,5 % |
TC-DD / DDE | 16 | FSS-16-E-GR10q FSS-16-I-GR8 FSS-16-L/P/H-GR10q | 16 | 15 | 87,0 % | 83,3 % | 75,0 % | 72,4 % | 66,1 % |
TC-DD / DDE | 21 | FSS-21-E-GR10q FSS-21-L/P/H-GR10q | 21 | 19,5 | 89,7 % | 86,7 % | 78,0 % | 73,9 % | 68,8 % |
TC-DD / DDE | 28 | FSS-28-E-GR10q FSS-28-I-GR8 FSS-28-L/P/H-GR10q | 28 | 24,5 | 89,1 % | 86,0 % | 80,3 % | 78,2 % | 73,9 % |
TC-DD / DDE | 38 | FSS-38-E-GR10q FSS-38-L/P/H-GR10q | 38,5 | 34,5 | 92,0 % | 89,6 % | 85,2 % | 84,1 % | 80,4 % |
TC | 5 | FSD-5-I-G23 FSD-5-E-2G7 | 5,4 | 5 | 72,7 % | 66,7 % | 58,8 % | 49,3 % | 41,4 % |
TC | 7 | FSD-7-I-G23 FSD-7-E-2G7 | 7,1 | 6,5 | 77,6 % | 72,2 % | 65,0 % | 55,7 % | 47,8 % |
TC | 9 | FSD-9-I-G23 FSD-9-E-2G7 | 8,7 | 8 | 78,0 % | 72,7 % | 66,7 % | 60,3 % | 52,6 % |
TC | 11 | FSD-11-I-G23 FSD-11-E-2G7 | 11,8 | 11 | 83,0 % | 78,6 % | 73,3 % | 66,7 % | 59,6 % |
T5 | 4 | FD-4-E-G5-16/150 | 4,5 | 3,6 | 64,9 % | 58,1 % | 50,0 % | 45,0 % | 37,2 % |
T5 | 6 | FD-6-E-G5-16/225 | 6 | 5,4 | 71,3 % | 65,1 % | 58,1 % | 51,8 % | 43,8 % |
T5 | 8 | FD-8-E-G5-16/300 | 7,1 | 7,5 | 69,9 % | 63,6 % | 58,6 % | 48,9 % | 42,7 % |
T5 | 13 | FD-13-E-G5-16/525 | 13 | 12,8 | 84,2 % | 80,0 % | 75,3 % | 72,6 % | 65,0 % |
T9-C | 22 | FSC-22-E-G10q-29/200 | 22 | 19 | 89,4 % | 86,4 % | 79,2 % | 74,6 % | 69,7 % |
T9-C | 32 | FSC-32-E-G10q-29/300 | 32 | 30 | 88,9 % | 85,7 % | 81,1 % | 80,0 % | 76,0 % |
T9-C | 40 | FSC-40-E-G10q-29/400 | 40 | 32 | 89,5 % | 86,5 % | 82,1 % | 82,6 % | 79,2 % |
T2 | 6 | FDH-6-L/P-W4,3x8,5d-7/220 | 5 | 72,7 % | 66,7 % | 58,8 % | |||
T2 | 8 | FDH-8-L/P-W4,3x8,5d-7/320 | 7,8 | 76,5 % | 70,9 % | 65,0 % | |||
T2 | 11 | FDH-11-L/P-W4,3x8,5d-7/420 | 10,8 | 81,8 % | 77,1 % | 72,0 % | |||
T2 | 13 | FDH-13-L/P-W4,3x8,5d-7/520 | 13,3 | 84,7 % | 80,6 % | 76,0 % | |||
T2 | 21 | FDH-21-L/P-W4,3x8,5d-7/ | 21 | 88,9 % | 85,7 % | 79,2 % | |||
T2 | 23 | FDH-23-L/P-W4,3x8,5d-7/ | 23 | 89,8 % | 86,8 % | 80,7 % | |||
T5-E | 14 | FDH-14-G5-L/P-16/550 | 13,7 | 84,7 % | 80,6 % | 72,1 % | |||
T5-E | 21 | FDH-21-G5-L/P-16/850 | 20,7 | 89,3 % | 86,3 % | 79,6 % | |||
T5-E | 24 | FDH-24-G5-L/P-16/550 | 22,5 | 89,6 % | 86,5 % | 80,4 % | |||
T5-E | 28 | FDH-28-G5-L/P-16/1150 | 27,8 | 89,8 % | 86,9 % | 81,8 % | |||
T5-E | 35 | FDH-35-G5-L/P-16/1450 | 34,7 | 91,5 % | 89,0 % | 82,6 % | |||
T5-E | 39 | FDH-39-G5-L/P-16/850 | 38 | 91,0 % | 88,4 % | 82,6 % | |||
T5-E | 49 | FDH-49-G5-L/P-16/1450 | 49,3 | 91,6 % | 89,2 % | 84,6 % | |||
T5-E | 54 | FDH-54-G5-L/P-16/1150 | 53,8 | 92,0 % | 89,7 % | 85,4 % | |||
T5-E | 80 | FDH-80-G5-L/P-16/1150 | 80 | 93,0 % | 90,9 % | 87,0 % | |||
T5-E | 95 | FDH-95-G5-L/P-16/1150 | 95 | 92,7 % | 90,5 % | 84,1 % | |||
T5-E | 120 | FDH-120-G5-L/P-16/1450 | 120 | 92,5 % | 90,2 % | 84,5 % | |||
T5-C | 22 | FSCH-22-L/P-2GX13-16/225 | 22,3 | 88,1 % | 84,8 % | 78,8 % | |||
T5-C | 40 | FSCH-40-L/P-2GX13-16/300 | 39,9 | 91,4 % | 88,9 % | 83,3 % | |||
T5-C | 55 | FSCH-55-L/P-2GX13-16/300 | 55 | 92,4 % | 90,2 % | 84,6 % | |||
T5-C | 60 | FSCH-60-L/P-2GX13-16/375 | 60 | 93,0 % | 90,9 % | 85,7 % | |||
TC-LE | 40 | FSDH-40-L/P-2G11 | 40 | 91,4 % | 88,9 % | 83,3 % | |||
TC-LE | 55 | FSDH-55-L/P-2G11 | 55 | 92,4 % | 90,2 % | 84,6 % | |||
TC-LE | 80 | FSDH-80-L/P-2G11 | 80 | 93,0 % | 90,9 % | 87,0 % | |||
TC-TE | 32 | FSMH-32-L/P-2GX24q=3 | 32 | 91,4 % | 88,9 % | 82,1 % | |||
TC-TE | 42 | FSMH-42-L/P-2GX24q=4 | 43 | 93,5 % | 91,5 % | 86,0 % | |||
TC-TE | 57 | FSM6H-57-L/P-2GX24q=5 FSM8H-57-L/P-2GX24q=5 | 56 | 91,4 % | 88,9 % | 83,6 % | |||
TC-TE | 70 | FSM6H-70-L/P-2GX24q=6 FSM8H-70-L/P-2GX24q=6 | 70 | 93,0 % | 90,9 % | 85,4 % | |||
TC-TE | 60 | FSM6H-60-L/P-2G8=1 | 63 | 92,3 % | 90,0 % | 84,0 % | |||
TC-TE | 62 | FSM8H-62-L/P-2G8=2 | 62 | 92,2 % | 89,9 % | 83,8 % | |||
TC-TE | 82 | FSM8H-82-L/P-2G8=2 | 82 | 92,4 % | 90,1 % | 83,7 % | |||
TC-TE | 85 | FSM6H-85-L/P-2G8=1 | 87 | 92,8 % | 90,6 % | 84,5 % | |||
TC-TE | 120 | FSM6H-120-L/P-2G8=1 FSM8H-120-L/P-2G8=1 | 122 | 92,6 % | 90,4 % | 84,7 % | |||
TC-DD | 55 | FSSH-55-L/P-GRY10q3 | 55 | 92,4 % | 90,2 % | 84,6 % | ] |
In addition, non-dimmable ballasts not included in table 17 shall be assigned an EEI depending on their efficiency as described in Table 18:
Energy efficiency index requirements for non-dimmable ballasts for fluorescent lamps not included in Table 17
ηballast | Energy Efficiency Index |
---|---|
≥ 0,94 * EBbFL | A3 |
≥ EBbFL | A2 |
≥ 1-0,75*(1-EBbFL) | A2 BAT |
Where EBbFL is defined in Annex II.3.g.
Furthermore, dimmable fluorescent lamp ballasts receive EEI classes according to the class into which the ballast would fall when it is operated at the 100 % lumen output, as described in Table 19.
Energy efficiency index requirements for dimmable ballasts for fluorescent lamps
Complied class at 100 % lumen output | Energy Efficiency Index of dimmable ballast |
---|---|
A3 | A1 |
A2 | A1 BAT |
Multi-wattage ballasts shall either be classified according to their efficiency under the lowest (worst) efficiency, or a relevant class shall be indicated for each operated lamp.
Three years after the entry into force of this Regulation:
for ballasts for high intensity discharge lamps, the efficiency of the ballast as defined in Annex II.1.d shall be indicated.
One year after this Regulation comes into force:
the power consumption of luminaires for fluorescent lamps without integrated ballast shall not exceed the sum of the power consumption of the incorporated ballasts when the lamps they are normally operating do not emit any light when other possible connected components (network connections, sensors etc.) are disconnected. If they cannot be disconnected, their power shall be measured and deducted from the result.
Three years after this Regulation comes into force:
Luminaires for fluorescent lamps without integrated ballast and for high intensity discharge lamps shall be compatible with ballasts complying with the third stage requirements, except luminaires with ingress protection grade at least IP4X.
The power consumption of luminaires for high intensity discharge lamps shall not exceed the sum of the power consumption of the incorporated ballasts when the lamps they are normally operating do not emit any light when other possible connected components (network connections, sensors etc.) are disconnected. If they cannot be disconnected, their power shall be measured and deducted from the result.
Eight years after this Regulation comes into force:
All luminaires for fluorescent lamps without integrated ballast and for high intensity discharge lamps shall be compatible with ballasts complying with the third stage requirements.
18 months after this Regulation comes into force:
Manufacturers of luminaires for fluorescent lamps without integrated ballast with total lamp lumen above 2 000 lumen shall provide at least the following information on free-access websites and in other forms they deem appropriate for each of their luminaire models. That information shall also be contained in the technical documentation file drawn up for the purposes of conformity assessment pursuant to Article 8 of Directive 2005/32/EC:
if the luminaire is placed on the market together with the ballast, information on the efficiency of the ballast according to Annex III.2.2, in accordance with the ballast manufacturer’s data;
if the luminaire is placed on the market together with the lamp, lamp efficacy (lm/W) of the lamp, in accordance with the lamp manufacturer’s data;
if the ballast or the lamp are not placed on the market together with the luminaire, references used in manufacturers' catalogues must be provided on the types of lamps or ballasts compatible with the luminaire (e.g. ILCOS code for the lamps);
maintenance instructions to ensure that the luminaire maintains, as far as possible, its original quality throughout its lifetime;
disassembly instructions.
Three years after this Regulation comes into force:
the information provision requirements of the first stage shall also apply to luminaires for high intensity discharge lamps with total lamp lumen above 2 000 lumen. In addition, all luminaires for high intensity discharge lamps shall indicate that they are designed for either clear and/or coated lamps within the meaning of Annex II.