Commission Directive 2010/36/EUShow full title

Commission Directive 2010/36/EU of 1 June 2010 amending Directive 2009/45/EC of the European Parliament and of the Council on safety rules and standards for passenger ships (Text with EEA relevance)

 Help about what version

What Version

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

This item of legislation originated from the EU

Legislation.gov.uk publishes the UK version. EUR-Lex publishes the EU version. The EU Exit Web Archive holds a snapshot of EUR-Lex’s version from IP completion day (31 December 2020 11.00 p.m.).

Status:

This is the original version (as it was originally adopted).

.1 Ships carrying more than 36 passengers
NEW CLASS B, C AND D SHIPS:
.1The ventilation system shall, in addition to paragraph 1 in Regulation II/32 of the 1974 SOLAS Convention, as in force on 17 March 1998, also be in compliance with subparagraphs .2.2 to .2.6, .2.8 and .2.9 of this Regulation.
NEW CLASS B, C AND D AND EXISTING CLASS B SHIPS:
.2In general, the ventilation fans shall be so disposed that the ducts reaching the various spaces remain within the main vertical zone.
.3Where ventilation systems penetrate decks, precautions shall be taken, in addition to those relating to fire integrity of the deck required by Regulation II-2/A/12.1, to reduce the likelihood of smoke and hot gases passing from one between-deck space to another through the system. In addition to insulation requirements contained in this Regulation, vertical ducts shall, if necessary, be insulated as required by the appropriate tables in Regulation 4.
NEW CLASS B, C AND D SHIPS:
.4Ventilation ducts shall be constructed of the following materials:
.1

ducts not less than 0,075 m2 in sectional area and all vertical ducts serving more than a single between-deck space shall be constructed of steel or other equivalent material;

.2

ducts less than 0,075 m2 in sectional area other than vertical ducts referred to in subparagraph .1.4.1 shall be constructed of non-combustible materials. Where such ducts penetrate “A” or “B” class divisions due regard shall be given to ensuring the fire integrity of the division;

.3

short lengths of duct, not in general exceeding 0,02 m2 in sectional area nor two metres in length, need not be non-combustible provided that all of the following conditions are met:

.1

the duct is constructed of a material of low fire risk to the satisfaction of the Administration of the flag State;

.2

the duct is used only at the terminal end of the ventilation system; and

.3

the duct is not located closer than 600 mm measured along its length to a penetration of an “A” or “B” class division, including continuous “B” class ceilings.

CLASS B, C AND D SHIPS CONSTRUCTED ON OR AFTER 1 JANUARY 2003:

instead of subparagraph .1 the following subparagraph .1a shall apply:

.1a

the duct shall be of a material which has low flame spread characteristics.

.5Stairway enclosures shall be ventilated and shall be served only by an independent fan and duct system which shall not serve any other spaces in the ventilation system.
NEW CLASS B, C AND D AND EXISTING CLASS B SHIPS:
.6All power ventilation, except machinery space and cargo space ventilation and any alternative system which may be required under subparagraph .9.2.6, shall be fitted with controls so grouped that all fans may be stopped from either of two separate positions which shall be situated as far apart as practicable. Controls provided for the power ventilation serving machinery spaces shall also be grouped so as to be operable from two positions, one of which shall be outside such spaces. Fans serving power ventilation systems to cargo spaces shall be capable of being stopped from a safe position outside such spaces.
NEW CLASS B, C AND D SHIPS:
.7Where public spaces span three or more open decks and contain combustibles such as furniture and enclosed spaces such as shops, offices and restaurants, the space shall be equipped with a smoke extraction system. The smoke extraction system shall be activated by the required smoke detection system and be capable of manual control. The fans shall be sized such that the entire volume within the space can be exhausted in 10 minutes or less.
.8Ventilation ducts shall be provided with suitably located hatches for inspection and cleaning, where reasonable and practicable.
.9Exhaust ducts from galley ranges in which grease or fat is likely to accumulate shall meet requirements of subparagraphs .9.2.3.2.1 and .9.2.3.2.2 and shall be fitted with:
.1

a grease trap readily removable for cleaning unless an alternative approved grease removal system is fitted;

.2

a fire damper located in the lower end of the duct which is automatically and remotely operated, and in addition a remotely operated fire damper located in the upper end of the duct;

.3

a fixed means for extinguishing a fire within the duct;

.4

remote control arrangements for shutting off the exhaust fans and supply fans, for operating the fire dampers mentioned in .2 and for operating the fire-extinguishing system, which shall be placed in a position close to the entrance to the galley. Where a multi-branch system is installed, means shall be provided to close all branches exhausting through the same main duct before an extinguishing medium is released into the system; and

.5

suitably located hatches for inspection and cleaning.

Back to top

Options/Help

Print Options

You have chosen to open the Whole Directive

The Whole Directive you have selected contains over 200 provisions and might take some time to download. You may also experience some issues with your browser, such as an alert box that a script is taking a long time to run.

Would you like to continue?

You have chosen to open Schedules only

The Schedules you have selected contains over 200 provisions and might take some time to download. You may also experience some issues with your browser, such as an alert box that a script is taking a long time to run.

Would you like to continue?

Close

Legislation is available in different versions:

Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.

Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

Opening Options

Different options to open legislation in order to view more content on screen at once

Close

More Resources

Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the EU Official Journal
  • lists of changes made by and/or affecting this legislation item
  • all formats of all associated documents
  • correction slips
  • links to related legislation and further information resources
Close

More Resources

Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the print copy
  • correction slips

Click 'View More' or select 'More Resources' tab for additional information including:

  • lists of changes made by and/or affecting this legislation item
  • confers power and blanket amendment details
  • all formats of all associated documents
  • links to related legislation and further information resources